DT1102 (PS)
Switch Configurable I/O Galvanic Isolator
Operating Instructions
Page 1: ...DT1102 PS Switch Configurable I O Galvanic Isolator Operating Instructions...
Page 2: ...icators configuration switches 8 3 5 Input output signal selection 9 3 6 Storage and transport 10 4 Mounting 11 4 1 General instructions 11 4 2 Main dimensions of the instrument 11 4 3 Mounting proced...
Page 3: ...ators 20 6 1 First power on 20 6 2 Front panel Indicators 20 7 Fault rectification 21 7 1 Fault finding 21 7 2 Repearing 21 8 Dismounting 22 8 1 Dismounting procedure 22 8 2 Disposal 22 9 Appendix 23...
Page 4: ...anual should be made available to these personnel and put into practice by them 1 3 Symbolism used Information tip note This symbol indicates helpful additional information Caution warning danger This...
Page 5: ...hazards or damage to system components through incorrect installing or adjustment 2 4 General safety instructions Using the DT1102 PS requiring the strict observance of standards regulations and guid...
Page 6: ...s The scope of delivery encompasses DT1102 PS tool for switch setting in case of shipping more instrument only one tool is enclosed documentation this operating instructions manual certification warra...
Page 7: ...ormation about the operating status of the device power on state error states Principle of operation The input current flows through the measuring resistor or the input voltage divides through the att...
Page 8: ...ches The following figure shows the indicators and the configuration switches on the DT1102 PS front panel 1 configuration switches for selection input output ranges 2 red error indicator shows the er...
Page 9: ...0 mA 4 20 mA 0 10 V 2 10 V Default setting 0 20 mA input 0 20 mA output all switches are in off state The following figure shows the input output signal range selection table The following figure show...
Page 10: ...in places whose climatic conditions are in accordance with chapter 9 1 Technical specification as described under the title Environmental conditions The packaging of DT1102 PS consist of environment f...
Page 11: ...tion where the operating conditions are in accordance with chapter 9 1 Technical specification as described under the title Operating conditions Mounting position The DT1102 PS is built in a plastic h...
Page 12: ...mounting doesn t need any tool 1 Tilt the instrument according to the figure put the instrument s mounting hole onto the upper edge of the rail figure step 1 2 Push the instrument s bottom onto the b...
Page 13: ...oss section insulation screening etc You may use either solid conductor or flexible conductor In case of using flexible conductor use crimped wire end The instrument can be connected with standard two...
Page 14: ...Be careful the polarity of the cables 1 Loosen terminal screws 2 Insert the wire ends into the open terminals according to the wiring plan 3 Screw the terminal in 4 Check the hold of the wires in term...
Page 15: ...example Be careful the polarity of the cables 1 Loosen terminal screws 2 Insert the wire ends into the open terminals according to the wiring plan 3 Screw the terminal in 4 Check the hold of the wires...
Page 16: ...ty of the cables 1 Loosen terminal screws 2 Insert the wire ends into the open terminals according to the wiring plan 3 Screw the terminal in 4 Check the hold of the wires in terminals by pulling on t...
Page 17: ...areful the polarity of the cables 1 Loosen terminal screws 2 Insert the wire ends into the open terminals according to the wiring plan 3 Screw the terminal in 4 Check the hold of the wires in terminal...
Page 18: ...areful the polarity of the cables 1 Loosen terminal screws 2 Insert the wire ends into the open terminals according to the wiring plan 3 Screw the terminal in 4 Check the hold of the wires in terminal...
Page 19: ...en on the data label When the instrument type designation ends with PS then the power supply terminal coloured black 2 Connect only in the complete absence of line voltage 3 Loosen terminal screws 4 I...
Page 20: ...proper working of the instrument or in certain situation may cause impairment of the instrument 6 2 Front panel Indicators In normal working mode Green on indicator lights red error indicator dark Und...
Page 21: ...ctive Green on indicator lights red error indicator flashes 1 sec periodically the instrument is defective Improper output signal disconnect the signal processing unit from the output check the input...
Page 22: ...ep 1 2 Lift the screwdriver handle until it possible to open the fixing assembly figure step 2 3 Keeping the screwdriver in this position lift the instrument bottom from the bottom edge of the rail fi...
Page 23: ...put resistance 3 M Output parameters voltage Output signal DC voltage Ranges 0 10 V 2 10 V Overdriving ability 11 V Load resistance 500 Output resistance 0 5 Transfer parameters Error of output 25 C 2...
Page 24: ...ria BURST Analogue input Main supply input PS Analogue outputs 4 kV 5 50 ns 5 kHz 2 kV 5 50 ns 5 kHz 1 kV 5 50 ns 5 kHz A criteria A criteria A criteria SURGE Analogue input Main supply input PS Analo...
Page 25: ...DT1102 PS 20220202 V0 25 start 9 2 Application example...
Page 26: ...DT1102 PS 26 20220202 V0...
Page 27: ...DT1102 PS 20220202 V0 27...
Page 28: ......