7.15. Analogue output limiting
Function
The analogue output works correspond with NAMUR
standard. For example the 4–20 mA type output has 3,8 mA
– 20,5 mA current range.
You can limit this range. For example: let the low output limit
is 12 mA and the high output limit is 17 mA. In this case if
calculated current is lower than 12 mA or higher than 17
mA, the output current will indicate the error state. (See:
7.16.: Analogue output error state disabling.)
1. Type-in the low and the high output limits. (In voltage
mode the typed value is desired voltage value x2)
The figure shows the factory default settings:
Sequence of operations
7.16. Analogue output error state disabling
Function
The checked check box of the instrument disables the
output error sate. In this case the analogue output can not
generate error current, the output current remains between
the low and the high values.
(See: 7.15.: Analogue output limiting.)
1. Check the check box for disabling the output error signal.
Sequence of operations