DT1010 xx xx
20180403-V1
21
7.6. Setting averaging
Function
The instrument performs cca. 12 measurements in each
seconds. (In 3 wire mode only 5 measurements). The
measurement result is generated as the average of several
measurements.
Here you can define the number of measurements that
should be used for calculating the averaged numerical
value. By increasing this number the signal stability
increases, but the signal settling time becomes lower.
[Default factory setting: 16]
1. Select the appropriate output signal by clicking the
button.
The figure shows the factory default setting.
Sequence of operations
Note: Selecting the „1” value the last measured result will
be transmitted. Measured results - measured before the last
measurement - have no effect on the output signal.
Settling time after stabilizing the input signal (4 wire mode):
Averaging number:
Settling time (sec):
1 0.1
2 0.2
4 0.4
8 0.7
16 1.4
32 2.7
64 5.4