ADIO WIRELESS BRIDGE USER’S MANAUL REV. 02
14
ADIO Command Reference Table
Main
command
Function Command
Name
Command Description
Default
Value
Value Range
help
Displays list of main commands
NA
No parameters
info
Displays device serial number
NA
No parameters
sample
Outputs sample inputs in mV to the
information port
NA
No parameters
set & get
chX.lvl.dovolts
Determines the Digital output voltage
level. Parameter is in millivolts. ch.1,
ch.2, ch.3 & ch.4
3300(3.3V)
0-10000 mV
ch.X.lvl.def
Determines the starting default
voltage level as well as the return
level for signal timeout.
0
0-10000 mV
ch.X.lvl.tmo
If a radio packet is not received, the
output channel will return to the value
set in ch.X.lvl.def. The io.txrate should
be set shorter than this timeout value
if used.
0
0-1800000ms
ch.X.token
Sets the channel communications
token. In order for I/O line passing,
channel tokens
must
match for a
specific channel to be set for I/O line
passing.
ch.1, ch.2, ch.3 & ch.4
Example: set ch.1.token 6
0 (Not
enabled)
0 – 4 million
ch.X.type
Sets the IO function type
ch.1, ch.2, ch.3, ch.4
0 = off
1 = Analog input 0-10V
2 = Analog output 0-10V
3 = Digital Input
4 = Digital ouput
5 = 4-20mA input
Example set ch.2.type 3 (sets channel
2 to a digital input).
1
0-5
ch.X.cd
Change detect parameter. When
enabled with a value of 1, 2 or 3 the
Wireless Bridge will send a
transmission when a change on a
Digital input is detected. 50ms
maximum rate.
0 = off
1 = rising edge
2 = falling edge
3 = both
0
0-3
cd.rate
Change detect sampling rate. Sets the
timing for the samples to be detected.
Only used for digital inputs.
0
50 –
1800000ms
defaults
Restores factory default settings.
NA
No parameters