background image

 

 

DIAGNOSTICS FUNCTION 

The operator can visualize the operating condition of the light curtains thanks to the 8 led positioned on both the RX and 
TX unit. SG. The figure below shows all signalling LEDs modes: 

OFF, ON, BLINKING, INDIFFERENT

 (Can be both On 

or Off depending on actual working mode)  

 

 

RX UNIT 

ESPE Working 

Mode 

Indication 

 

Suggested Action 

INTERLOCK 

Free beams 
OSSDs OFF 

 

User can restart device in normal operation 
activating RESTART line. 

Intercepted beams 
OSSDs OFF 

 

User must free beams path before activating 
RESTART line. 

NORMAL 

OPERATION 

OSSD ON 

 

 

SAFE OSSD 

OFF 

 

 

 

- EDM 

active 

 

 

FAILURE 

LOCKOUT 

Failure on OSSD(s) 

 

Activate RESET line. If error persists 
contact Datalogic Technical Support. 

FAILURE 

LOCKOUT 

Failure on micro-
processor(s) 

 

Activate RESET line. If error persists 
contact Datalogic Technical Support. 

FAILURE 

LOCKOUT 

Failure on optics 
 

 

Activate RESET line. If error persists 
contact Datalogic Technical Support. 

FAILURE 

LOCKOUT 

failure on EDM 
 

 

Check EDM feedback line and EDM 
configuration. Activate RESET line. 

FAILURE 

LOCKOUT 

Failure on restart 
 

 

Check RESTART line connection. 
Activate RESET line. 

FAILURE 

LOCKOUT 

Comunication failure 

 

Check the correct mounting of terminator 
cap. Activate RESET line. 

FAILURE 

LOCKOUT 

Configuration failure 

 

Re-operate Basic Configuration. If error 
persists contact Datalogic Technical 
Support. 

CRITICAL 

FAILURE 

LOCKOUT 

Generic Non-resettable 
failure 

 

Turn ON/OFF ESPE. Shown Failure 
Code corresponds to failures above with 
steady leds. 

ESPE OFF 

Power supply failure 

 

Check Power Supply Connection. If error 
persists contact Technical Support. 

Summary of Contents for SG2 M Series

Page 1: ...e operations Please carefully read the instructions for the correct functioning before powering the light curtain Precautions to be observed for the choice and installation of the device Make sure that the protection level assured by the SG2 M device is compatible with the real danger level of the machine to be controlled according to EN ISO 13849 1 and EN 62061 The outputs OSSD of the ESPE must b...

Page 2: ...RRIDE1 green 5 OSSD2 pink 6 EDM yellow 7 MUTING ENABLE black 8 OSSD1 grey 9 OVERRIDE2 red 10 MUTING LAMP violet 11 OVERRIDE STATUS grey pink 12 EARTH red blue M12 5 pole 1 24V brown 2 MUTING2 white 3 0V blue 4 MUTING1 black 5 N C grey SG2 M TX M12 5 pole 1 24V brown 2 TEST white 3 0V blue 4 EARTH black 5 N C ...

Page 3: ...mitter until the yellow SYNC 1 LED is OFF This condition shows the effective alignment of the first synchronisation beam B Rotate the emitter pivoting on the lower optics axis until the yellow SYNC 2 LED is OFF C Delimit the area in which alignment is good and steady through some micro adjustments for the first and then for the second unit so to have the maximum alignment LEVEL and then place both...

Page 4: ... to enter Basic Configuration Mode A Test Pattern is shown on led interface carefully check that ALL led are lit in sequence from 1 to 8 then current configuration is shown B Choose function to set by SELECT button selected led blinks C Configure selected function with ENABLE button switch led on off Repeat B C steps until desired configuration is visualized E Keep CONFIRM button pressed to author...

Page 5: ...port FAILURE LOCKOUT Failure on micro processor s Activate RESET line If error persists contact Datalogic Technical Support FAILURE LOCKOUT Failure on optics Activate RESET line If error persists contact Datalogic Technical Support FAILURE LOCKOUT failure on EDM Check EDM feedback line and EDM configuration Activate RESET line FAILURE LOCKOUT Failure on restart Check RESTART line connection Activa...

Page 6: ... UNIT ESPE Working Mode Indication Action EMISSION Emission TEST Test If undesired Test check TEST line connection FAILURE LOCKOUT Failure on micro processor s Activate RESET line If error persists contact Datalogic Technical Support FAILURE LOCKOUT Failure on optics Activate RESET line If error persists contact Datalogic Technical Support FAILURE LOCKOUT Comunication failure Check the correct mou...

Page 7: ...oduct In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures Datalogic S r l Via S Vitalino 13 40012 Calderara di Reno Italy Tel 39 051 3147011 Fax 39 051 3147205 www datalogic com Helpful links at www datalogic com Contact Us Terms and Conditions Support The warranty period for this product is 36 months See General Term...

Reviews: