6. Maintenance & repair 

 

6.1 Types of error 

If any error occurs, it indicates such error and stops operation. 

When abnormal, its contents are displayed on the window of the keypad. 

 

Causes of faults and corrective actions 

Fault 
Code

 

Type 

Indication 

Causes of errors 

Corrective actions 

E001 

Input 

Over-current 

PV Error 

Over current from solar module   

Check the solar module then operate the inverter.       

If the problem isn’t solved, contact us. 

E002 

Input 

Over-voltage 

DC OV 

Over voltage from solar module 

Check the solar module then operate the inverter.       

If the problem isn’t solved, contact us. 

E004 

Input 

DC-LINK 

Over-voltage 

DC-Link OV 

Over voltage from DC-LINK of 

the inverter 

Check the solar module then operate the inverter.       

If the problem isn’t solved, contact us. 

E005 

Input 

DC-LINK 

Under-voltage 

DC-Link UV 

Under voltage from DC-LINK 

of the inverter 

Check the solar module then operate the inverter.       

If the problem isn’t solved, contact us. 

E006 

Grid   

Over-current 

Over Current 

Over current in grid output 

Check grid status and contact your electricity authority.   

Then if the problem isn’t solved, contact us   

E007 

Grid 

Over-voltage 

Over voltage 

Abnormal grid voltage 

Check grid status and contact your electricity authority.   

Then if the problem isn’t solved, contact us 

E008 

Grid 

Under-voltage 

Under voltage 

Abnormal grid voltage 

Check grid status and contact your electricity authority.   

Then if the problem isn’t solved, contact us 

E010 

Grid   

Over-frequency 

Over 

frequency 

Abnormal grid frequency 

Check grid status and contact your electricity authority.   

Then if the problem isn’t solved, contact us 

E011 

Grid 

Under-frequency 

Under 

frequency 

Abnormal grid frequency 

Check grid status and contact your electricity authority.   

Then if the problem isn’t solved, contact us 

E019 

PWM fault 

(Input) 

Over 

Current 2 

Inverter’s internal problem 

Contact us immediately 

E020 

PWM fault 

(Output) 

Over 

Current 2 

Inverter’s internal problem 

Contact us immediately 

E022 

Over heating 

Over   

heat 

Inverter’s over heating   

Pls. try to operate inverter and if the problem isn’t solved,   

pls. contact us immediately   

E023 

Earth fault 

(DC) 

Earth fault 

Leakage of current 

(Short circuit status) 

Check earth and insulation status then, if the problem isn’t 

solved, contact us.   

E030 

Consecutive fault 

Cont. fault 

Same fault happens 

consecutively 

Pls. try to operate inverter and if the problem isn’t solved,   

pls. contact us immediately 

 

 

 

 

Summary of Contents for DSP-123K5-OD

Page 1: ...DASS Tech Photovoltaic Grid Connected Inverter DSP 123K5 OD ver1 0 Operation and Installation Manual...

Page 2: ...place 9 3 3 Terminal connection diagram 10 3 4 Wiring 11 3 5 Cautions for mounting the inverter to the wall 14 4 Operation 15 4 1 Display 15 4 2 Basic mode 15 4 3 Operation method 17 5 Function 17 5 1...

Page 3: ...te when the cover is open It could cause electric shock as high voltage terminal or electric charging is exposed outside Do not adjust switch when your hands are wet It could cause electric shock Do n...

Page 4: ...ase check external conditions Do not pile up beyond the limited level or height Do not open the cover while transported Do not drop or damage with shock as this device is a precision one 2 Application...

Page 5: ...llowed by the guidelines in this manual Do not drop or add damage to the inverter as this device is a pr cised one Do Class 3 grounding work 200V class for the inverter Don t place other home applianc...

Page 6: ...t impair the body seriously use the inverter after understanding the application or installation manual enough in using the inverter 2 1 2 Appearance of the product 2 1 3 Confirmation of Products Afte...

Page 7: ...normal operation impossible or cause a serious declination in lifetime In the event of worst case the inverter may be damaged by fire and use this device in right manner in accordance with the content...

Page 8: ...maintain the maximum power point through MPPT 6 Easy Parallel Operation If the capacity of solar cells increases the inverter can be added and connected for extension of capacity without any additiona...

Page 9: ...e IP 65 Outdoor Equipment noise 50 dB or less External dimension W x L x H 305 380 135 5 mm Full weight 9 9kg External interface RS 485 Monitoring Device Option DSP WR5 DSP ZR5 Wire Wireless RS485 232...

Page 10: ...e temperature 10 50 3 Avoid hot and humid place Relative humidity should be less than 90 No dewfall 4 Install the inverter at the place with no direct sun shine 5 As the inverter is a high temperature...

Page 11: ...Solar cell power DC Solar input power Connected with of Solar cell power RS485 Communication terminal Connect to signal line of the monitoring system AC Grid power connection terminal Inverter output...

Page 12: ...use a case or sash screw as an earth terminal For earth wire use exclusive earth wire complying with the standard Connect the earth terminal to the spot adjacent to the inverter The earth cable must...

Page 13: ...g cable and terminal Terminal used when connecting cable and connector Nut to fix the connecter inside the inverter To easily classify Inside Connector and Outside Connector is to check the difference...

Page 14: ...d of connector and inverter Notice Connect only the same polarity shown above 2 AC Connector wiring Connector Terminal Connector Terminal Connector Terminal Turn the nut to be fixed Nut Connector Term...

Page 15: ...See the wiring diagram 3 3 3 5 Cautions for mounting the inverter to the wall Installation Remove press fit spanner for the inverter by using a tool like long nose plier Remove Wall BKT from the inver...

Page 16: ...es the operation status of the inverter Green light inverter generation is normal Red flickering Fault 4 2 Basic mode 2 lines 16 characters LCD When the inverter power is ON information on the LCD is...

Page 17: ...2 5 Daily today generated power Display Unit Today today s generated power Wh Present power generated 4 2 6 Daily previous day generated power Display Unit DAY 1 previous day s generated power Wh Pre...

Page 18: ...er always monitors the grid power and it stops automatically in abnormal status 5 Function 5 1 Descriptions 5 1 1 Grid monitoring Whether the system voltage is normal or abnormal is determined by the...

Page 19: ...tion deletes the fault records occurred in the past and sets to ready mode Controlling the inner keypad randomly shall cause malfunction of the inverter You should contact DASS tech 5 1 4 Fault 1 Faul...

Page 20: ...contact us E007 Grid Over voltage Over voltage Abnormal grid voltage Check grid status and contact your electricity authority Then if the problem isn t solved contact us E008 Grid Under voltage Under...

Page 21: ...the date time and indications on the fault If the product does not work normally check the follows for requesting customer service 1 Name of model 2 Serial number of the product 3 Purchased place 4 Pu...

Page 22: ...ure occurred under normal using condition within the warranty period your product can be tested and repaired for free Charged A S For following cases A S could be provided at a cost The product is out...

Page 23: ...ustomer service 82 1588 7468 Tel 82 43 218 5670 Fax 82 43 218 5671 Headquarters DASS Tech Co Ltd 109 Yangcheongsongdae gil Ochang eup Cheongwon gu Cheongju si Chungbuk Korea http www dasstech com Ver...

Reviews: