DASS 3.0i LV (DSP-123i-ODS)
User manual
Copyright © DASS Tech Co., Ltd
- 55 -
temperature.
Env
temp is too high
ID65
UnrecoverHwAc
OCP
The grid current is
too high,and has
cause
unrecoverable
hardware fault
ID65-ID70 are internal faults of inverter,
turn OFF the “DC switch”, wait for 5 minutes,
then turn ON the “DC switch”. Check whether
the fault is rectified. If no, please contact
technical support.
ID66 UnrecoverBusOV
P
The bus voltage is
too high,and has
cause
unrecoverable fault
ID67 UnrecoverIacRms
Unbalance
The grid current is
unbalance,and has
cause
unrecoverable fault
ID68 UnrecoverIpvUnb
alance
The input current is
unbalance,and has
cause
unrecoverable fault
ID69
UnrecoverVbusU
nbalance
The bus voltage is
unbalance,and has
cause
unrecoverable fault
ID70
Unrecover OCP
Instant
The grid current is
too high,and has
cause
unrecoverable fault
ID71 UnrecoverPvConf
igSetWrong
Incorrect input
mode
Check the input mode(parallel mode/
independent mode) setting of inverter according
to Section 6.3 (C) 6.Input Mode of this user
manual, If it’s incorrect, change it according to
Section 6.3 (A) 10.Set Input mode of this manual
ID74 UnrecoverIPVInst
ant
The input current is
too high,and has
cause
unrecoverable fault
ID74-ID77 are internal faults of inverter,
turn OFF the “DC switch”, wait for 5 minutes,
then turn ON the “DC switch”. Check whether
the fault is rectified. If no, please contact
technical support.
ID75
UnrecoverWRIT
EEEPROM
The EEPROM is
unrecoverable
ID76
UnrecoverREAD
EEPROM
The EEPROM is
unrecoverable
ID77
Unrecover Relay
Fail
Relay has happen
permanent fault
ID81
Over Temp
Derating
The inverter has
derated because of
the temperature is
too high
Ensure the installation position and
installation method meet the requirements of
Section 3.4 of this user manual.Check whether
the ambient temperature of the installation
position exceeds the upper limit. If yes, improve
ventilation to decrease the temperature.
ID82
Over Freq
Derating
The inverter has
derated because of
Inverter automatically reduce the output
power when the frequency of electrical grid is