Capacity of fire pump is measured in gallons per minute. The usual method of measurement is to
determine the pressure of the jet of water leaving a given size of nozzle by means of a “Pitot Gage”
from which the capacity is computed mathematically.
A Pitot Gage consists of a small tube adapted to a point directly into the hose nozzle from the
center of the issuing stream, the other end of the tube being connected to an accurate pressure
gage.
The nozzle jet drives straight into the Pitot tube and converts the velocity of the jet to pressure
which is an accurate measure of velocity of the water as it leaves the nozzle. The tip of the Pitot
tube should be one-half the diameter of the nozzle away from nozzle tip while taking reading.
Table No. 2 gives nozzle capacities for various Pitot Gage readings.
If a Pilot gage is not available approximate pump capacities can be determined by reference to
Table No.3
Summary of Contents for ZSP
Page 64: ......
Page 66: ......
Page 67: ...DRIVELINE INSTALLATION J3311 1 DSSP AUGUST 2008 Supersedes J3311 1 HVTSS Dated February 2005 ...
Page 89: ......
Page 130: ......
Page 133: ......
Page 135: ...7 31 1200503 ...
Page 136: ...7 32 1200503 ...
Page 139: ...7 35 1200503 ...
Page 140: ...7 36 1201002 ...
Page 142: ...7 66 ...
Page 143: ...7 65 ...
Page 144: ......
Page 146: ......
Page 147: ......
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......