Danyon DA-HP-16-230 Installation And Owner'S Manual Download Page 44

13 INFORMATION SERVICING

1) Checks to the area

Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is 

minimized. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.

2) Work procedure

Works shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work 

is being performed.

3) General work area

All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out, work in confined sapces 

shall be avoided. The area around the work space shall be sectioned off. Ensure that the conditions within the area have been made safe by 

control of flammable material. 

4) Checking for presence of refrigerant

The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially 

flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. no sparking, 

adequately sealed or intrinsically safe.

5) Presence of fire extinguisher

If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be 

available to hand. Have a dry power or CO

2

 fire extinguisher adjacent to the charging area.

6) No ignition sources

No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained 

flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion.

All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation,repairing, removing 

and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around 

the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. NO SMOKING signs shall be displayed.

7) Ventilated area

Ensure that the area is in the open or that it’s adequately ventilated before breaking into the system or conducting any hot work. A degree of 

ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and 

preferably expel it externally into the atmosphere.

8) Checks to the HVAC equipment

Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s 

maintenance and service guidelines shall be followed. If in doubt consult the manufacturer s technical department for assistance. The following 

checks shall be applied to installations using flammable refrigerants:

•  The charge size is in accordance with the room size within which the refrigerant containing parts are installed;

•  The ventilation machinery and outlets are operating adequately and are not obstructed;

•  If an indirect refrigerating circuit is being used, the secondary circuits shall be checked for the presence of refrigerant; marking to the 

equipment continues to be visible and legible.

•  Marking and signs that are illegible shall be corrected;

•  Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode 

refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are •  

suitably protected against being so corroded.

9) Checks to electrical devices

Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that 

could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be 

corrected immediately but it is necessary to continue operation, and adequate temporary solution shall be used. This shall be reported to the 

owner of the equipment so all parties are advised.

Initial safety checks shall include:

•  That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;

•  That there no live electrical components and wiring are exposed while charging, recovering or purging the system;

•  That there is continuity of earth bonding.

10) Repairs to sealed components

a) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any 

removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently 

operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.

b) Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way 

that the level of protection is affected. This shall include damage to cables, excessive number of connections,terminals not made to original 

specification, damage to seals, incorrect fitting of glands, etc.

•  Ensure that apparatus is mounted securely.

•  Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable 

atmospheres. Replacement parts shall be in accordance with the manufacture's specifications.

42

Summary of Contents for DA-HP-16-230

Page 1: ...OWNER S MANUAL Air to Water Heat Pump System Tri Thermal Monobloc IMPORTANT NOTE Thank you very much for purchasing our product Before using your unit please read this manual carefully and keep it for...

Page 2: ...REFRIGERANT 05 4 INSTALLATION SITE 05 5 INSTALLATION PRECAUTIONS 08 6 OVERVIEW OF THE UNIT 11 7 TEST RUN AND FINAL CHECKS 26 8 MAINTENANCE AND SERVICE 26 9 TURN OVER TO CUSTOMER 27 10 OPERATION AND PE...

Page 3: ...te personal protection equipment such as gloves and safety glasses while installing the unit or carrying out maintenance activities Contact your dealer for any further assistance Improper installation...

Page 4: ...odour The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continuously operating ignition sources example open flames an operating gas appliance and...

Page 5: ...falling from its mount Install the unit on a foundation that can withstand its weight Insufficient physical strength may cause the equipment to fall and possible cause injury Perform specified instal...

Page 6: ...the air or where volatile flammables such as paint thinner or gasoline are handled These types of gases might cause a fire Where the air contains high levels of salt such as near the ocean Where volt...

Page 7: ...s than 6 kg of fluorinated greenhouse gases shall not be subject to leak checks For unit that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2 equivalent or more but of less than...

Page 8: ...lling the unit in a place exposed to strong wind pay special attention to the following Strong winds of 5 m sec or more blowing against the unit s air outlet causes a short circuit suction of discharg...

Page 9: ...be sure to follow the instructions described below 4 1 2 Prevent sunshine As the outdoor temperature is measured via the monobloc air thermistor make sure to install the monobloc in the shade or a ca...

Page 10: ...ain off too much water through the pressure relief valve Water quality should be complied with EN 98 83 EC Directives NOTE Connect the water supply to the filling valve and open the valve Make sure al...

Page 11: ...the air inlet or aluminum fins of the unit Do not use the grips in the fan grills to avoid damage The unit is top heavy Prevent the unit from falling due to improper inclination during handling CAUTI...

Page 12: ...in front of the outlet side 300mm A 2 In case obstacles exist in front of the air inlet In case of installing multiple units in lateral connection per row 5 2 2 In case of multiple row installation fo...

Page 13: ...install a ground fault circuit interrupter 30 mA Failure to do it may cause electrical shock Be sure to install the required fuses or circuit breakers 6 1 1 Precautions on electrical wiring work The g...

Page 14: ...27 28 Code 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Monobloc Wire controller Stop valve Check valve Three way valve 1 SV1 Buffer tank Buffer tank electric heater IBH1 Zone 1 pump P_O Three way valve 2 S...

Page 15: ...diagram for electrical wiring works the electric wiring diagrams are located on the service panel Install the wires and fix the cover firmly so that the cover may be fit in properly Field wiring guid...

Page 16: ...DHW mode the slave unit only can run in heating mode DHW mode and cool mode can t run at the same time All slave units can run in cooling or heating mode and the runing mode and temperature setting ch...

Page 17: ...after the balance tank Please ensure that the maximum interval between power on times of all units does not exceed 2 minutes If it exceeds the maximum communication detection time of the master and sl...

Page 18: ...087 0 66 0 66 8kW 3kW heater 220 240 50 50 198 198 264 264 29 30 32 32 40 40 14 5 0 17 0 17 1 4 1 4 0 087 0 087 0 66 0 66 220 240 15 5 12kW 14kW 50 50 198 198 264 264 26 28 32 32 24 0 17 0 17 1 4 1 4...

Page 19: ...E 1 12V 2 B1 3 A1 4 E1 5 A 6 B 7 E 8 H1 9 H2 10 N L LPS Fuse CN32 CN33 CN31 TBH 1 SL1 2 SL2 3 1ON 4 1OFF 5 2ON 6 2OFF 7 3ON 8 IBH1 9 N 10 N 11 N 12 N 13 4ON 14 4OFF 15 3OFF 16 MV1 1 MV2 2 P_O 3 P_M 4...

Page 20: ...N 9 N 10 N 11 N 12 N 13 N 14 N 15 AHS2 16 E 1 12V 2 B1 3 A1 4 E1 5 A 6 B 7 E 8 H1 9 H2 10 The ground fault circuit interrupter must be a high speed type breaker of 30 mA 0 1 s Flexible cord must meet...

Page 21: ...10 N 11 N 12 N 13 4ON 14 4OFF 15 3OFF 16 MV1 1 MV2 2 P_O 3 P_M 4 P_T 5 P_S 6 P_R 7 AHS1 8 N 9 N 10 N 11 N 12 N 13 N 14 N 15 AHS2 16 E 1 12V 2 B1 3 A1 4 E1 5 A 6 B 7 E 8 H1 9 H2 10 0 2A load can conne...

Page 22: ...nect the cable to the appropriate terminals as shown in the picture Fix the cable reliably a Procedure Connect the cable to the appropriate terminals as shown in the picture Fix the cable reliably SV4...

Page 23: ...AHS1 8 N 9 N 10 N 11 N 12 N 13 N 14 N 15 AHS2 16 E 1 12V 2 B1 3 A1 4 E1 5 A 6 B 7 E 8 H1 9 H2 10 CN32 CN33 CN31 L1 L2 L3 N L1 L2 L3 N TBH 1 SL1 2 SL2 3 1ON 4 1OFF 5 2ON 6 2OFF 7 3ON 8 IBH1 9 N 10 N 1...

Page 24: ...6 8 L N Auxiliary heat source KM5 Power supply 7 5 3 1 A1 A2 2 4 6 8 ATCO TCO 10 For backup electric heating L N CN32 CN33 CN31 TBH 1 SL1 2 SL2 3 1ON 4 1OFF 5 2ON 6 2OFF 7 3ON 8 IBH1 9 N 10 N 11 N 12...

Page 25: ...iggnal are off the unit operates as below The unit will not operate DHW mode and the TBH is invalid disinfect function is invalid The max running time for cooling heat ing is SG RUNNING TIME then unit...

Page 26: ...m 1N ON OFF SW3 Slave unit Master unit E4 12V B1 A1 E1 CN37 E 12V B1 A1 E1 A B E H1 H2 CN33 Power supply Please use the shielded wire and the shield layer must be grounded On Off switch Fuse Distribut...

Page 27: ...the cord from being pulled out by external force make sure it is fixed securely Power cord Insulation tube Circular wiring terminal Power Supply Circuit Breaker Manual switch Wire Distribution Box 25...

Page 28: ...to be carried out at regular intervals This maintenance has to be carried out by your local technician ELECTRIC SHOCK Before carrying out any maintenance or repairing activity must switch off the powe...

Page 29: ...he refrigerant leaks in the room contact with a fire of a burner a heater or a cooker may result in a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer whe...

Page 30: ...l not become hot immediately at the beginning of the heating operation 3 5 minutes ago depends on the indoor and outdoor temperature until the indoor heat exchanger become hot then becomes hot During...

Page 31: ...new sensor Plate heat exchanger refrigerant liquid pipe is abnormal d5 1 Check the resistance of the sensor 2 The sensor connector is loosen Reconnect it 3 The sensor connector is wet or there is wate...

Page 32: ...ter circuit are completely open 5 Check if the water filter needs cleaning 6 Insufficient water flow 7 Detect the amount of refrigerant Plate heat exchanger inlet water temperature is too low L5 1 Che...

Page 33: ...the temperature Controller is reset it can be reset manually Multiple master control failure C1 1 When an internal machine is connected with two line controllers if both line controllers are set as ma...

Page 34: ...hether the power supply voltage of the monobloc is too low resulting in abnormal reversing of the 4 way valve 3 If the fault still cannot be solved consult the manufacturer Outdoor exhaust temperature...

Page 35: ...n plug off the connector for several times to make sure the valve is working correctly Low pressor switch protection H2 High pressure sensor failure H3 1 Check whether the sensor is connected properly...

Page 36: ...95 996 535 DC motor Horizontal DC inverter dual rotary Fin coil R32 1400g Unit model 220 240V 1N 50Hz 8kW 17A 30A 3300W 3000W 15 5A 3600W 3000W Electric heater Rated water pressure Filter mesh Min wat...

Page 37: ...0 1 0 3MPa Heating mode Cooling mode Domestic hot water mode 25 35 C 5 43 C 25 43 C Outlet water heating model Outlet water cooling model 25 65 C 5 20 C Water outlet temperature range Operating temper...

Page 38: ...al rotary Fin coil R32 1740g Unit model 220 240V 1N 50Hz 12kW 27 5A 29 5A 25 5A 5400W Electric heater Rated water pressure Filter mesh Min water flow flow switch Pump Type Max head Power input Expanss...

Page 39: ...ng mode Cooling mode Domestic hot water mode 25 35 C 5 43 C 25 43 C Outlet water heating model Outlet water cooling model 25 65 C 5 20 C Water outlet temperature range Operating temperature Storage te...

Page 40: ...ual rotary Fin coil R32 1740g Unit model 380 415V 3N 50Hz 12kW 9 5A 10 0A 9 0A 5400W Electric heater Rated water pressure Filter mesh Min water flow flow switch Pump Type Max head Power input Expanssi...

Page 41: ...ng mode Cooling mode Domestic hot water mode 25 35 C 5 43 C 25 43 C Outlet water heating model Outlet water cooling model 25 65 C 5 20 C Water outlet temperature range Operating temperature Storage te...

Page 42: ...otor Horizontal DC inverter dual rotary Fin coil R32 1740g Unit model 318 415V 3N 50Hz 5800W 9000W 22 5A 23 0A 5400W 9000W 22 0A 6200W 9000W Electric heater Rated water pressure Filter mesh Min water...

Page 43: ...essure R5 4 20 60 C 0 1 0 3MPa Heating mode Cooling mode Domestic hot water mode 25 35 C 5 43 C 25 43 C Outlet water heating model Outlet water cooling model 25 65 C 5 20 C Water outlet temperature ra...

Page 44: ...all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to in...

Page 45: ...the sensitivity may not be adequate or may need re calibration Detection equipment shall be calibrated in a refrigerant free area Ensure that the detector is not a potential source of ignition and is...

Page 46: ...inders shall be completed with pressure relief valve and associated shut off valves in good working order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs The recov...

Page 47: ......

Reviews: