page 7 of 10
Oilbuner
Type Gulliver RG0.R
GB
Combustion adjustment:
To suit the required appliance output, fit the nozzle then adjust the pump pressure, and the
air damper opening in accordance with the following schedule.
Nozzles recommended:
Delavan:
Type W – B
Danfoss:
Type S – B
Monarch:
Type R
Steinen:
Type S – Q
K:\framen\instrukt\Dantherm\RG\Engelsk\RG0r\RG0R.fm-I2-020916-dm/lbk
Adjustment
Nozzle
Pump pressure
Burner output
Air damper
[GPH]
angle
[bar]
[kg/h ± 4%]
adjustment
0,40
60°
11
1,4
1,0
0,50
60°
12
1,9
1,8
0,60
60°
12
2,3
2,8
Nozzle and pump pressure on highest capacity:
Nozzle
Pump pressure
Burner output
Air damper
[GPH]
angle
[bar]
[kg/h ± 4%]
adjustment
0,60
60°
12
2,3
2,2
0,65
60°
12
2,5
2,7
0,75
60°
13
3,0*
3,9
If the oil burner has to run in the highest ca-
pacity the diffuser disc has to be changed
(see page 6) and the enclosed sticker is to
be put on the model sign.
*At maximum capacity the isolation (3,
page 4) has to be removed in order to incre-
ase the air capacity.