page 7 of 9
Oilbuner
Type Gulliver RG3
GB
Combustion adjustment:
To suit the required appliance output, fit the nozzle then adjust the pump pressure, and the
air damper opening in accordance with the following schedule.
Nozzles recommended:
Delavan:
Type W – B
Danfoss:
Type S – B
Monarch:
Type R
Steinen:
Type S – Q
K:\framen\instrukt\Dantherm\RG\Engelsk\RG3\RG3.fm-I2-021108-dm/lbk
Adjustment
Nozzle
Pump pressure
Burner output
Combustion head
adjustment
Air damper
[GPH]
angle [°]
[bar]
[kg/h ± 4%]
adjustment
1,75
60
10,5
6,9
0
0,5
1,75
60
12
7,3
0
0,6
2,00
60
12
7,9
1
0,8
2,25
60
12
9,5
3
1,1
2,50
60
12
10,2
3,5
1,2
3,00
60
12
12,5
5
2,0
3,50
60
12
14,4
6
2,5
3,50
60
14
15,2
6
2,9