3. INSTALLATION
16
3.3.9 Water cooled condenser
The heat pump in a DanX XWPS swimming pool unit may be fitted with a water-cooled
condenser for transfer of surplus heat, which is not used for heating the return/supply air, to
the pool or sanitary water. The drawing below shows Dantherm’s suggestion on how to
connect the water cooled condenser to the swimming pools water supply.
1.
Main pump for pool water
2.
Temperature sensor pool water (separate water temperature control)
3.
Manual shut down valve
4.
Pump for water cooled condenser (control signal from DanX control panel)
5.
Water consumption gauge
6.
Regulation valve
7.
Temperature sensor (separate water temperature control with on/off signal to DanX
control panel)
8.
3 way valve (separate water temperature control)
10.
Temperature gauge
13.
Air realise valve
14.
Non return valve
15.
Separate heat exchanger for pre heating sanitary water
NB!
Piping material must be suitable for chlorine water.
Please be aware of the specified max. water volume (se table below), as a to high water
velocity can destroy the water cooled condenser and cooling circuit of the DanX unit.
XWPS
2/4
3/6
5/10
7/14
9/18
12/24
16/32
Max
water
L/h
800 1250 1900 2750 2750 5300 5300