8. APPENDIX
37
8.1 VLT 2800 parameter settings two speed with pressure transducer
Parameter Description
Value
Function / unit
Comment
100
Configuration 3
Process
closed
loop
101
Torque characteristic
3
Variable torque medium
102
Motor power
*
kW
* See motor type plate
103
Motor voltage
400
V
104
Motor frequency
50
Hz
105
Motor current
*
A
* See motor type plate
106
Motor speed
*
rpm
* See motor type plate
128
Thermal motor protection
2
Thermistor trip
Motor with thermistor
“
“
4
ETR trip
Motor without thermistor
201
Output frequency low
15
Hz
202
Output frequency high
Hz
Depending on motor/fan
204
Minimum reference
*
Pa
* Set pressure range of
pressure transducer
(4.3.3)
205
Maximum reference
*
Pa
* Set pressure range of
pressure transducer
(4.3.3)
207
Ramp up time 1
60
sec.
208
Ramp down time 1
60
sec.
215
Preset reference low
*
%
* Low air volume (4.3.2)
216
Preset reference high
*
%
* High air volume (4.3.2)
303
Input terminal 19
25
Thermistor
Motor with thermistor
“
“
9 Reversing
Motor
without
thermistor
305
Input terminal 29
22
Preset ref.
308
Input terminal 53
2
Feedback
323
Relay output 1-3
10
Alarm
414
Minimum feedback
*
Pa
* See parameter 204
415
Maximum feedback
*
Pa
* See parameter 205
416
Process unit
11
Pa
440
Process PID proportional gain
1.5
Sec.
441
Process PID integration time
20
sec.
444
Process PID low pass filter
time
2 sec.
All other parameters are standard Danfoss factory settings.