9. APPENDIX
52
9.5 Technical data DanX 1
General
Air volume range high speed
m
3
/h
500
– 1250
Air volume nominal
m
3
/h
1000
Supply air filter
F7 / ePM1 55%
Exhaust air filter
M5 / ePM10 70%
Heating coil
RR
2 / 3
Coil connection
“
3/8
Drip tray connection
“
1
DanX 1 XD
Length
mm
1570
Width
mm
515
Height
mm
1750
Weight
kg
254
Electrical connection
V
1 x 230 + N
Max full load current
A
5.0
Max. power consumption
kW
1.2
Max. main fuse
A
10
DanX 1 HP
Length
mm
1570
Width
mm
515
Height
mm
1750
Weight
kg
279
Refrigerant
kg
1.0 / R407c
GWP
1653
PED
1
Electrical connection
V
1 x 230 + N
Max full load current
A
8.7
Max. power consumption
kW
1.9
Max. main fuse
A
10