4. CONTROLS
22
•
Heating_Coil_Pump (Actual status if pump is running)
•
DX_Cooling (Actual status for signal to DX cooling coil)
•
Duct_Dampers (Actual duct damper position)
•
Bypass_Damper (Actual by pass damper position)
•
Heat_Demand (Actual demand for heating in %. A demand < 50% means cooling
demand, > 50% means heating demand)
•
Dehumidify_Demand (Actual demand for dehumidification in %)
•
Room_Temp_CalcSet (Actual room temperature set point)
•
Supply_Air_Temp_CalcSet (Actual supply air temperature set point)
•
Room_Humidity_CalcSet (Actual room humidity set point)
•
External_Signal (Actual status for external signal)
The points under Unit Status give an overall view of the actual running situation of the unit.
All points are read only for the Guest / Operator and can only be set into manual with the
System Administrator password.
4.4.5 Unit Configuration menu
When entering the Unit Configuration you will see the following start display in the program:
Here you will find the following unit configuration points:
•
Filter_Check_Date (see 4.3.5.1)
•
Heating_Coil_Configuration (see 4.3.5.2)
•
Wake_Up_Temperature_Configuration (see 4.3.5.3)
•
Wake_Up_Humidity_Configuration (see 4.3.5.3)
•
Signal_External_Configuration (see 4.3.5.4)
•
WCC_Pump_Exercice_Configuration (see 4.3.5.5)
•
Closed_Mode_Cooling (see 4.3.5.6)
The points under Unit Configuration should be set once when the unit is commissioned and
not be changed afterwards. All points are read only for the Guest / Operator and can only be
changed with the System Administrator password.