4.0 DATA SHEET
AA300/AA500AVH
For accurate application sizing consult Dantherm Ltd.
1 mm WG = 9.8pa
Boiler not required for AA versions without LPHW.
1 mhd = 1.4psi
1 L/min = 0.22 gall/min
R407c Global warming potential (GWP) 1774.
MODEL
Units
AA300
AA500
Air temperature limits
Minimum
ºC
15
15
Maximum
ºC
36
36
Dehumidification duty
Via heat pump (30C/60% RH)
L/hr
3.6
4.5
Heat to air (all models)
Via heat pump
kW
4.4
6.1
Via LPHW @ 80°C
kW
7.3
7.5
Heat pump + LPHW
kW
9.8
11.7
Recommended boiler capacity
(AA+ Air LPHW models only)
Recommended boiler capacity
kW
7.3
7.5
LPHW flow rate
L/min
10
10
LPHW Pressure drop at rated flow
mhd
2.9
2.9
Maximum system working pressure
bar
6
6
Heat to pool water (AA+ air and
water LPHW models only)
Via heat pump
kW
n/a
n/a
Via LPHW @ 80°C
kW
18
18
Pool water flow rate
L/min
15
15
Pool water pressure drop at rated flow
mhd
2.8
2.8
Recommended boiler capacity
(AA+ Air and water LPHW
models only)
Recommended boiler capacity
kW
25.3
25.5
LPHW flow rate
L/min
21
21
LPHW Pressure drop at rated flow
mhd
4.2
4.2
Maximum system working pressure
bar
6
6
Electrical
V/ph/Hz
230V/ ~1N/50Hz
Total power Cconsumed (nominal)
kW
2.1
2.3
Minimum supply capacity (Max F.L.A.)
A
13
13
Maximum supply fuse 1 ph N
A
20
20
Main fan
Air flow (anemometer at air on filter, wet evaporator)
m³/hr
1300 ±10%
1800 ±10%
Design condition external static pressure
Pa
95
110
Maximum external static pressure
Pa
300
250
Design condition Amps
1 ph N
A
1.6
2.8
FLA:- 1 ph N
A
5.2
5.2
Compressor
Nominal power consumed
kW
1.9
1.9
LRA:- 1 ph N
A
42
42
RLA:- 1 ph N
A
9
9
Soft start Amps 1 ph N
A
23
23
General data
Hermetic system
Gas charge (R407c)
kg
2.6
2.6
Carbon dioxide equivalent
tonnes
4.6
4.6
LPHW battery volume
litres
1.15
1.15
IP rating
IP
22
22
Physical dimensions
Width (Unpacked)
mm
730
730
Depth (Unpacked)
mm
1025
1025
Height (Unpacked)
mm
850
850
Weight approx. (AA un-packed no options)
kg
111
111
noise level at 1m
dB(A)
61
61
29
SD611250 ISSUE 8
Summary of Contents for Calorex AA300AVH
Page 1: ...AA300AVH AA500AVH Owner installation manual SD611250 issue 8...
Page 2: ...2 SD611250 ISSUE 8 AA300AVH AA500AVH TECHNICAL MANUAL...
Page 21: ...COMPRESSOR CONTACTOR SEE BELOW FAN RELAY SEE BELOW R01 R02 R03 R04 R05 19 SD611250 ISSUE 8...
Page 23: ...ELEC CONTROL POWER CIRCUIT AA AIR LPHW CONTINUED R01 R02 R04 R03 R06 R05 21 SD611250 ISSUE 8...
Page 34: ...34 SD611250 ISSUE 8 AA300AVH AA500AVH TECHNICAL MANUAL...
Page 35: ...35 SD611250 ISSUE 8...