INSTALLATION WITH OPTIONAL FEATURES
Ensure duct work pressure drop does not exceed resistance given in data
sheet.
If unit is located in a plant room at pool hall air temperatures, any ambient air
ducting must be heavily insulated.
Recommend fresh air/spring return dampers to be fitted to Fresh air ductwork
for sub zero ambient applications in case of power failure.
Ensure duct work pressure drop does not exceed resistance given in data sheet.
If the static resistance drops below the figure stated in the data sheet and a greater air flow is required, it is possible to
change the speed of the fan from non 'F' to 'F'.
With the machine isolated move the blue wire connected to terminal 17 on the fan motor to terminal 18 on the fan
motor. (See circuit diagram section 2.5)
If unit is located in a plant room at pool hall air temperatures, any ambient air ducting must be heavily insulated.
Recommend fresh air/exhaust spring return dampers to be fitted to ductwork for sub zero ambient
applications in case of power failure.
OPTIONAL FLEXIBLE
DUCTING FLANGE
FILTER ACCESS PANEL
OPTIONAL FLEXIBLE
DUCTING FLANGE
SER
VICE
PANEL
CONSOLE POSITION
AL
TERNA
TIVE
CONSOLE POSITION
SERVICE
ACCESS TO ELECTRIC BOX
800
AIR ON
BLANKING PLA
TE
FOR OPTIONAL
FRESH AIR GRILLE 4 HOLES DIA 6 ON
125mm DIA.
CONTROL P
ANEL
CONNECTION POINT
RED LAMP 12V
REMO
TE CONTROL PANEL ON INDICA
TION
11
SD611250 ISSUE 8
Summary of Contents for Calorex AA300AVH
Page 1: ...AA300AVH AA500AVH Owner installation manual SD611250 issue 8...
Page 2: ...2 SD611250 ISSUE 8 AA300AVH AA500AVH TECHNICAL MANUAL...
Page 21: ...COMPRESSOR CONTACTOR SEE BELOW FAN RELAY SEE BELOW R01 R02 R03 R04 R05 19 SD611250 ISSUE 8...
Page 23: ...ELEC CONTROL POWER CIRCUIT AA AIR LPHW CONTINUED R01 R02 R04 R03 R06 R05 21 SD611250 ISSUE 8...
Page 34: ...34 SD611250 ISSUE 8 AA300AVH AA500AVH TECHNICAL MANUAL...
Page 35: ...35 SD611250 ISSUE 8...