background image

 •  Check current draw and voltage levels on the 

mains. The values for the compressor electri-
cal motor can be directly displayed on the fre-
quency converter control panel.

 •  The optimum compressor suction superheat is 

around 6K.

 •  Eventual reverse rotation can be detected by 

following phenomena; the excessive noise, 
no pressure differential between suction and 
discharge, and line warming rather than imme-
diate cooling. A service technician should be 
present at initial start-up to verify that wiring 
from drive to compressor is properly phased 
and that the compressor is rotating in the cor-
rect direction. 

 •  Note that a 300 seconds period is necessary be-

tween 2 starts, a shorter period will be not al-
lowed by the drive. The minimum running time 
is 12s for each start.

11 – Check with running compressor

  Check current draw and voltage. Measure-

ment of amps and volts during running condi-
tions must be taken at other points in the power 
supply, not in the compressor electrical box.
 •  Check suction superheat to reduce risk of slug-

ging.

 •  Observe the oil level at start and during opera-

tion to confirm that the oil level remains vis-
ible. Excess foaming in oil sight glass indicates 
refrigerant on the sump.

 •  Monitor the oil sight glass for 1 hour after sys-

tem equilibrium to ensure proper oil return to 
the compressor. This oil check has to be done 
over the speed range to guarantee:

  -   a good oil return at low speed with minimum 

gas velocity.

  -   a good oil management at high speed with 

maximum oil carry over.

 •  Respect the operating limits.
 •  Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm / 0.06 inch require 
corrective measures such as tube brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side 
as far as possible from the compressor. The 
compressor must be operating during this pro-
cess.

 •  Do not overcharge the system.
 •  Never release refrigerant to atmosphere.
 •  Before leaving the installation site, carry out 

a general installation inspection regarding 
cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference 
for future inspections.

 •  Compressor failure to build up pressure: Check 

all bypass valves in the system to ensure that 
none of these has been opened. Also check 
that all solenoid valves are in their proper posi-
tion.

 •  Abnormal running noise: Ensure the absence 

of any liquid flood-back to the compressor by 
means of measuring the return gas superheat 
and compressor sump temperature. The sump 
should be at least 6K above the saturated suc-
tion temperature under steady-state operating 
conditions.

 •  The high-pressure switch trips out: Check con-

denser operations (condenser cleanliness, fan 
operation, water flow and water pressure valve, 
water filter, etc.). If all these are OK, the problem 
may be due to either refrigerant overcharging 
or the presence of a noncondensable (e.g. air, 
moisture) in the circuit.

 •  The low-pressure switch trips out: Check evap-

orator operations (coil cleanliness, fan opera-
tions, water flow, water filter, etc.), liquid refrig-
erant flow and pressure drops (solenoid valve, 
filter dryer, expansion valve, etc.), refrigerant 
charge.

 •  Low refrigerant charge: The correct refrigerant 

charge is given by the liquid sight glass indica-
tion, the condenser delta T in relation to the 
refrigerant pressure tables (pressure-tempera-
ture), the superheat and the sub-cooling, etc. 
(if additional charge is deemed necessary, refer 
to section 8).

 •  Compressor short cycling: The number of cy-

cles shall never exceed 6 starts per hour.

12 – Maintenance

  Internal pressure and surface temperature are 

dangerous and may cause permanent injury. Main-
tenance operators and installers require appropri-
ate skills and tools. Tubing temperature may exceed 
100°C / 212°F and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 
regulations are performed.
To prevent system related compressor problems, 

following periodic maintenance is recommend-
ed:
 •  Verify that safety devices are operational and 

properly set.

 •  Ensure that the system is leak tight.
 •  Check the compressor current draw by reading 

one of the parameters via Modbus.

 •  Confirm that the system is operating in a way 

consistent with previous maintenance records 
and ambient conditions.

 •  Check that all electrical connections are still ad-

equately fastened.

 •  Keep the compressor clean and verify the ab-

sence of rust and oxidation on the compressor 
shell, tubes and electrical connections.

 •  Acid / moisture content in system and oil 

should be checked regularly.

13 - Warranty

Always transmit the model number and serial 
number with any claim filed regarding this prod-
uct.
Use the fault memory of the frequency con-
verter to recover the fault descriptions before 
initializing the system and even before shutting 
off the power. 
Variable speed drive model and serial number 
must also be transmitted with the claim.
The product warranty may be void in following 
cases:
 •  Absence of nameplate.
 •  External modifications; in particular, drilling, 

welding, broken feet and shock marks.

 •  Compressor opened or returned unsealed.
 •  Rust, water or leak detection dye inside the 

compressor.

 •  Use of a refrigerant or lubricant not approved 

by Danfoss.

 •  Any deviation from recommended instructions 

pertaining to installation, application or main-
tenance.

 •  Use in mobile applications.
 •  Use in explosive atmospheric environment.
 •  No model number or serial number transmit-

ted with the warranty claim.

14 – Disposal

Danfoss recommends that compressors 
and compressor oil should be recycled 
by a suitable company at its site.

Danfoss A/S

6430 Nordborg

Denmark

4 | © Danfoss | DCS (CC) | 2017.07

8510286P01B - FRCC.PI.039.A3.02 

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This 

also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trade-

marks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Summary of Contents for VZL028

Page 1: ... under nitrogen gas pressure between 0 3 and 0 4 bar 4 and 6 psi Do not disassemble bolts plugs fittings etc unless all pressure has been relieved from the compressor A B C D E F G H Operating limits Quick connect spade terminals push push push Electrical connections All the above limits temperatures and speeds are secured by parameters in the drive and application controller softwares VLZ028 VLZ0...

Page 2: ...O 05 12 24 V OUT COM 04 18 DIGI IN 19 DIGI IN 27 DIGI IN 29 DIGI IN 20 COM D IN N RS 485 69 P RS 485 68 Com RS 485 61 RELAY 2 CDS803 Legends Ana Analogue Dig Digital in Input out Output COM Common NC Normally closed NO Normally open Open loop Process loop 91 92 93 3 phases mains input x x 95 Earth x x 42 45 0 4 20 mA Analague Output or Digital Output 50 10V DC Output 53 0 10V or 4 20mA Analague In...

Page 3: ... located in the frequency converter package For further details refer to the appli cation guidelines Mounting The base frame of the frequency converter must be very well fixed to the sup port to ensure a very good continuity between the ground potential of all electrical panels and electrical boxes of the system Wiring All control wires have to be of a screeened design The cable for electrical mo ...

Page 4: ...s coil cleanliness fan opera tions water flow water filter etc liquid refrig erant flow and pressure drops solenoid valve filter dryer expansion valve etc refrigerant charge Low refrigerant charge The correct refrigerant charge is given by the liquid sight glass indica tion the condenser delta T in relation to the refrigerant pressure tables pressure tempera ture the superheat and the sub cooling ...

Reviews: