Basic connections

 -  Depending on the frequency converter ver-

sion, the physical position of individual con-
nectors may differ from below diagram.

  -   Always make sure that the compressor termi-

nals T1, T2, T3 are connected to the frequency 
converter terminals 96, 97, 98 respectively.

 -  The compressor motor cable must be shielded 

and the armoured part must be connected to 
ground on both cable ends; at the side of the 
compressor and at the side of the frequency con-
verter.

 -  Use an EMC cable gland for cable installation and 

perfect grounding; The metallic terminal box of 
the compressor has a paint-free surface around 

the connection hole for better conductivity.

 

-  A low pressure safety switch is mandatory 

to avoid compressor vacuum operation.

 -  At start-up, verify that the compressor rotates 

in the right direction and pumps.

R

E

LA

Y

 1

L1

91

L1

U

96

T1/U

L2

92

L2

V

97

T2/V

L3

93

L3

W

98

T3/W

95

PE

PE

99

45

0/4-20 mA A OUT / DIG OUT

42

0/4-20 mA A OUT / DIG OUT

50

+10 V OUT

NC

53

A IN

NO

02

03

54

A IN

COM

01

55

COM A IN/OUT

NC

06

NO

05

12

+24 V OUT

COM

04

18

DIGI IN

19

DIGI IN

27

DIGI IN

29

DIGI IN

20

COM D IN

N RS-485

69

P RS-485

68

Com RS-485

61

R

E

LA

Y

 2

C

D

S8

03

Legends: 

Ana: Analogue

Dig: Digital

in: Input

out: Output

COM: Common

NC: Normally-closed

NO: Normally-open

Open loop

Process loop

91,92,93

3 phases mains input

x

x

95

Earth

x

x

42,45

0/4-20 mA Analague Output or Digital Output

-

-

50

+10V DC Output

-

-

53

0-10V or 4-20mA Analague Input

x

-

54

0-10V or 4-20mA Analague Input

-

x

55

Com Analague In/Out

x

-

12

+24V output

-

-

18

External On/Off(NO)

x

x

19

Digital Input

-

-

27

Safety Device

x

x

29

Digital Input

-

-

20

Com Digital Input

-

-

98

To Compressor T3

x

x

97

To Compressor T2

x

x

96

To Compressor T1

x

x

99

Earth

x

x

03,02,01

Relay 1

-

-

06,05,04

Relay 2

-

-

69,68

RS485 Bus

-

-

61

RS485 Bus Com

-

-

-: Optional connection

X: Mandatory connection

The CDS803 frequency converter is factory 
preset with parameters for the open loop 
control principle. The process loop control 
principle can be selected by changing 
parameters in the «Quick menu».

Open loop: preset on input 53
0 - 10 V control

Frequency converter in slave mode
Process loop: preset on input 54
 4 - 20 mA control

Frequency converter under own PID controller

Instructions

2 |  © Danfoss | DCS (CC) | 2017.07

8510286P01B - FRCC.PI.039.A3.02

Summary of Contents for VZL028

Page 1: ... under nitrogen gas pressure between 0 3 and 0 4 bar 4 and 6 psi Do not disassemble bolts plugs fittings etc unless all pressure has been relieved from the compressor A B C D E F G H Operating limits Quick connect spade terminals push push push Electrical connections All the above limits temperatures and speeds are secured by parameters in the drive and application controller softwares VLZ028 VLZ0...

Page 2: ...O 05 12 24 V OUT COM 04 18 DIGI IN 19 DIGI IN 27 DIGI IN 29 DIGI IN 20 COM D IN N RS 485 69 P RS 485 68 Com RS 485 61 RELAY 2 CDS803 Legends Ana Analogue Dig Digital in Input out Output COM Common NC Normally closed NO Normally open Open loop Process loop 91 92 93 3 phases mains input x x 95 Earth x x 42 45 0 4 20 mA Analague Output or Digital Output 50 10V DC Output 53 0 10V or 4 20mA Analague In...

Page 3: ... located in the frequency converter package For further details refer to the appli cation guidelines Mounting The base frame of the frequency converter must be very well fixed to the sup port to ensure a very good continuity between the ground potential of all electrical panels and electrical boxes of the system Wiring All control wires have to be of a screeened design The cable for electrical mo ...

Page 4: ...s coil cleanliness fan opera tions water flow water filter etc liquid refrig erant flow and pressure drops solenoid valve filter dryer expansion valve etc refrigerant charge Low refrigerant charge The correct refrigerant charge is given by the liquid sight glass indica tion the condenser delta T in relation to the refrigerant pressure tables pressure tempera ture the superheat and the sub cooling ...