Electrical data, connections and wiring
Fuses
Danfoss recommends using the fuses listed
below to protect service personnel and property
in case of component break-down in the
frequency converter.
For circuit breakers, Moeller types have been
tested and are recommended.
Voltage range
From network to frequency converter
From frequency converter to compressor
Type
mm²
AWG
Type
mm²
AWG
380 - 480 V
CDS803-11kW
6
10
VLZ065
6
10
Note: The wire size in the guideline is the maximum wire size that connectors can accept but not the actual needed cable. The needed
cable size should be specified by the OEM depending on the unit design, ambient temperature, the wire material, current, etc...
Wire sizes
Below table lists maximum wiring sizes for the motor compressor power supply cables.
from network
to drive
from drive to
to compressor
Circuit breaker
Power input
I
Model
Power
UL Compliant fuses
Non -UL
Recommended cir‐
cuit breaker
Bussmann
Maximum
fuse
IP20
[kW]
Type RK5
Type RK1
Type J
Type T
Type G
Moeller type
3 × 380-480 V
VLZ065
11
FRS-R-80
KTS-R80
JKS-80
JJS-80
63
PKZM4-50
The CDS803 frequency converter generates by
design a compressor soft start with a default
initial ramp up refer to ‘Manage speed limit’.
Current inrush will not exceed the frequency
converter maximum current.
Basically seen from the mains, the inrush peak
reachs a level which is only a few percent more
than the rated nominal current.
Soft-start control
14