background image

AE21-1355 R4 

October 2017 

 
 

 

© 2017 Emerson Climate Technologies, Inc.

 

Digital Capacity Control for Copeland Discus

 Refrigeration Compressors 

 

TABLE OF CONTENTS 

 

Safety Instructions ................................................................ 2

 

Safety Icon Explanation ................................................ 2

 

Instructions Pertaining to Risk of Electrical Shock, Fire, 
or Injury to Persons ...................................................... 3

 

Safety Statements ........................................................ 3

 

Introduction ........................................................................... 4

 

Theory of Operation .............................................................. 4

 

Nomenclature ....................................................................... 5

 

Digital Performance .............................................................. 5

 

Operating Envelope .............................................................. 5

 

Control .................................................................................. 5

 

Control Requirements with Copeland

 Digital Compressor 

Controller .............................................................................. 7

 

Compressor Wiring ............................................................... 7

 

Control Requirements with CoreSense Diagnostics ............. 8

 

Master Controller .................................................................. 8

 

Recommended Application Settings for the Modulation on 
Copeland Discus Digital Compressors .................................. 8

 

Solenoid Valve/Gaskets ........................................................ 8

 

Thermistor ............................................................................. 8

 

Multiple Compressor Application ........................................... 9

 

General Guidelines and More Information .......................... 10

 

 

 

TABLE OF FIGURES   

 

Figure 1 Copeland Discus Digital Unloaded Operation 

(Shown on a Copeland 3D Discus) ....................................... 4

 

Figure 2 Copeland Discus Digital Loaded View (shown on a 

Copeland 3D Discus) ............................................................ 5

 

Figure 3 Typical Modulated Power Reduction (for 3D Discus 

Digital) .................................................................................. 6

 

Figure 4 Loaded vs Time ...................................................... 6

 

Figure 5 Copeland(R) Digital Compressor Controller ............. 7

 

Figure 6 Compressor Controller Wiring Diagram .................. 7

 

 

 
 

Revision Tracking R4

 
Pg. 4 

– Note related to 6D Discus Digital availability 

removed. 
Pg. 5 

– Note related to 6D Discus Digital availability 

removed. 
Pg. 8 

– Title renamed to “Control Requirements with 

CoreSense Diagnostics” 
Pg. 8 

– Reference to Intelligent Store Discus™ v2.x 

changed to CoreSense Diagnostics 
Pg. 8 

– Reference to Intelligent Store Discus changed 

to CoreSense Diagnostics 
Pg. 8 

– Link to E2 web page updated. 

Pg. 9 

– “Multiple Compressor Application” modified. 

Pg. 10 - Reference to AE8-1351 changed to AE8-1368 
"CoreSense™ Diagnostics v2.11 for Copeland 
Discus™ Compressors" 

 

 

 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

Summary of Contents for COPELAND 3DSDR17ME-TFD

Page 1: ... and More Information 10 TABLE OF FIGURES Figure 1 Copeland Discus Digital Unloaded Operation Shown on a Copeland 3D Discus 4 Figure 2 Copeland Discus Digital Loaded View shown on a Copeland 3D Discus 5 Figure 3 Typical Modulated Power Reduction for 3D Discus Digital 6 Figure 4 Loaded vs Time 6 Figure 5 Copeland R Digital Compressor Controller 7 Figure 6 Compressor Controller Wiring Diagram 7 Revi...

Page 2: ... lifetime of the compressor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which if not ...

Page 3: ...and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be used Failure to follow these warning...

Page 4: ...he 3D By varying the percentage of duty cycle that the compressor is loaded and unloaded capacity control between 10 and 100 can be achieved During blocked suction operation the flow of suction gas is blocked to all cylinders on a single bank therefore there is no gas to compress and the power consumption is significantly lower The unloader piston mechanism that controls flow of suction gas into t...

Page 5: ...iscus compressor envelopes The head fan return gas and oil cooler requirements are the same as those for the standard Discus compressors Control Capacity modulation is achieved by energizing and de energizing the solenoid valve When the solenoid valve is de energized the compressor capacity is 100 When the solenoid valve is energized the compressor capacity is zero Therefore the capacity achieved ...

Page 6: ... 2017 Emerson Climate Technologies Inc 6 AE21 1355 R4 Figure 3 Typical Modulated Power Reduction for 3D Discus Digital Figure 4 Loaded vs Time ...

Page 7: ... Digital Compressor Controller inside the electrical enclosure near the compressor contactor wire routing for compressor power wiring will be easier in this position The maximum wire terminal screw torque is 7 in lbs The Digital Compressor Controller will operate in any mounting orientation where the green POWER LED is at the top Mount the Digital Compressor Controller such that all LEDs are visib...

Page 8: ... Emerson com OPI The compressor motor should only be restarted after an appropriate time delay The digital modulation cycle time recommended is 20 seconds for other values check with your Application Engineer The minimum load and unload times should be limited to 2 seconds These described load and unload times will give the compressor an operating range during a 20 second cycle from 10 load up to ...

Page 9: ...e on a 4D you have continuous capacity from 50 to 100 therefore when selecting a 4D digital compressor you should have a fixed compressor behind it that is 50 100 of the full load of the digital compressor Example1 You have selected a 4DAXF47KL TSK This compressor capacity is about 47 000 Btu per hour 50 capacity is about 23 500 Then D 47 000 BTU h As the first fixed capacity compressor you must c...

Page 10: ...ow or contact your Application Engineer AE4 1135 Cooling Requirements for Copelametic and Copeland Discus Compressors AE4 1287 Copeland Discus Demand Cooling AE4 1334 Low Condensing Temperature Bulletin AE8 1328 Copeland Digital Compressor Controller AE8 1368 CoreSense Diagnostics v2 11 for Copeland Discus Compressors AE4 1357 Upgrade Procedures for Parallel Applications Using Digital Capacity Con...

Page 11: ...4012 167 C 0 01250 15 C 8 29400 30 C 0 80560 75 C 0 14800 120 C 0 03900 168 C 0 01226 14 C 6 89570 31 C 0 77200 76 C 0 14310 121 C 0 03793 169 C 0 01203 13 C 6 52190 32 C 0 74010 77 C 0 13850 122 C 0 03690 170 C 0 01180 12 C 6 17110 33 C 0 70960 78 C 0 13400 123 C 0 03590 171 C 0 01157 11 C 5 84150 34 C 0 68060 79 C 0 12970 124 C 0 03494 172 C 0 01134 10 C 5 53190 35 C 0 65300 80 C 0 12550 125 C 0...