24 VLT
®
Soft Starter Pocket Guide
NEMA 250 is a product standard for enclosure design and performance.
NEMA
Protection against solid objects
Approx. IP equivalent
1
Indoor, protection from contact.
IP 23
2
Indoor, limited protection from
dirt and water.
IP 30
3
Outdoor, some protection from rain,
sleet, windblown dust and ice.
IP 64
3R
Outdoor, some protection from rain,
sleet and ice.
IP 32
4
Indoor or outdoor, some protection from
windblown dust, rain, splashing water,
hose-directed water and ice.
IP 66
4X
Indoor or outdoor, some protection
from corrosion, windblown dust, rain,
splashing water, hose-directed water
and ice.
IP 66
6
Indoor or outdoor, some protection from
ice, hose-directed water, entry of water
when submerged at limited depth.
IP 67
12
Indoor, protection from dust, falling dirt
and dripping non-corrosive liquids.
IP 55
13
Indoor, protection from dust, spraying
water, oil and non-corrosive liquids.
IP 65
Warning:
Conversion from NEMA to IEC (IP) degrees of enclosure not
to be used
for converting from IEC to NEMA.
Please refer to NEMA publication 250, 2003.
NEMA ratings
Summary of Contents for VLT
Page 1: ...Pocket Guide VLT Soft Starter the single speed drive MAKING MODERN LIVING POSSIBLE...
Page 2: ......
Page 61: ......
Page 62: ...62 VLT Soft Starter Pocket Guide...