4.10.3 Ferraz Fuses - HSJ
Model
SCR I
2
t (A
2
s)
Supply Voltage
(< 440 VAC)
Supply Voltage
(< 575 VAC)
Supply Voltage
(< 690 VAC)
MCD5-0021B
1150
HSJ40**
HSJ40**
Not suitable
MCD5-0037B
8000
HSJ80**
HSJ80**
MCD5-0043B
10500
HSJ90**
HSJ90**
MCD5-0053B
15000
HSJ110**
HSJ110**
MCD5-0068B
15000
HSJ125**
HSJ125**
MCD5-0084B
51200
HSJ175
HSJ175**
MCD5-0089B
80000
HSJ175
HSJ175
MCD5-0105B
125000
HSJ225
HSJ225
MCD5-0131B
125000
HSJ250
HSJ250**
MCD5-0141B
320000
HSJ300
HSJ300
MCD5-0195B
320000
HSJ350
HSJ350
MCD5-0215B
320000
HSJ400**
HSJ400**
MCD5-0245C
320000
HSJ450**
HSJ450**
MCD5-0360C
238000
Not suitable
Not suitable
MCD5-0380C
320000
MCD5-0428C
320000
MCD5-0595C
1200000
MCD5-0619C
1200000
MCD5-0790C
2530000
MCD5-0927C
4500000
MCD5-1200C
4500000
MCD5-1410C
6480000
MCD5-1600C
12500000
** Two series connected fuses required per phase,
MCD 500 Operating Instruction
4 Electrical Installation
MG.17.K2.02 - VLT
®
is a registered Danfoss trademark
27
4