4.4.1 In-line Connection (Bypassed)
NB!
Models MCD5-0021B - MCD5-0215B are internally bypassed. Models MCD5-0245C - MCD5-1600C require an external bypass contactor.
AC-53b
3-30:330
AC-53b
4-20:340
AC-53b
4.5-30:330
MCD5-0021B
21 A
17 A
15 A
MCD5-0037B
37 A
31 A
26 A
MCD5-0043B
43 A
37 A
30 A
MCD5-0053B
53 A
46 A
37 A
AC-53b
3-30:570
AC-53b
4-20:580
AC-53b
4.5-30:570
MCD5-0068B
68 A
55 A
47 A
MCD5-0084B
84 A
69 A
58 A
MCD5-0089B
89 A
74 A
61 A
MCD5-0105B
105 A
95 A
78 A
MCD5-0131B
131 A
106 A
90 A
MCD5-0141B
141 A
121 A
97 A
MCD5-0195B
195 A
160 A
134 A
MCD5-0215B
215 A
178 A
148 A
MCD5-0245C
255 A
201 A
176 A
MCD5-0360C
360 A
310 A
263 A
MCD5-0380C
380 A
359 A
299 A
MCD5-0428C
430 A
368 A
309 A
MCD5-0595C
620 A
540 A
434 A
MCD5-0619C
650 A
561 A
455 A
MCD5-0790C
790 A
714 A
579 A
MCD5-0927C
930 A
829 A
661 A
MCD5-1200C
1200 A
1200 A
1071 A
MCD5-1410C
1410 A
1319 A
1114 A
MCD5-1600C
1600 A
1600 A
1353 A
4.4.2 AC-53 Rating for Bypassed Operation
All ratings are calculated at altitude of 1000 metres and ambient temperature of 40
°
C.
MCD 500 Operating Instruction
4 Electrical Installation
MG.17.K2.02 - VLT
®
is a registered Danfoss trademark
19
4