![Danfoss VLT PROFIBUS DP MCA 101 Programming Manual Download Page 51](http://html1.mh-extra.com/html/danfoss/vlt-profibus-dp-mca-101/vlt-profibus-dp-mca-101_programming-manual_3708540051.webp)
Selecting control mode for
8-53 Start Select
and
parameter 8-54 Reversing Select
:
If
[0] Digital input
is selected, the terminals control the start
and reversing functions.
Terminal
Bit 06/15
Function
0
0
Stop/Anti-clockwise
0
1
Stop/Anti-clockwise
1
0
Start/Clockwise
1
1
Start/Clockwise
Table 8.5 [0] Digital input
If
[1] Serial communication
is selected, activate commands
only when given via serial communication.
Terminal
Bit 02/03/04
Function
0
0
Stop/Anti-clockwise
0
1
Start/Clockwise
1
0
Stop/Anti-clockwise
1
1
Start/Clockwise
Table 8.6 [1] Serial communication
If
[2] Logic AND
is selected, activate both signals to perform
the function.
Terminal
Bit 02/03/04
Function
0
0
Stop/Anti-clockwise
0
1
Stop/Anti-clockwise
1
0
Stop/Anti-clockwise
1
1
Start/Clockwise
Table 8.7 [2] Logic AND
If
[3] Logic OR
is selected, activation of 1 signal activates
the function.
Terminal
Bit 02/03/04
Function
0
0
Stop/Anti-clockwise
0
1
Start/Clockwise
1
0
Start/Clockwise
1
1
Start/Clockwise
Table 8.8 [3] Logic OR
Selecting control mode for
8-55 Set-up Select
and
8-56 Preset Reference Select
:
If
[0] Digital input
is selected, the terminals control the set-
up and preset reference functions.
Terminal
Bit 00/01, 13/14 Function
Msb
Lsb
Msb
Lsb
Preset ref., Set-up no.
0
0
0
0
1
0
0
0
1
1
0
0
1
0
1
0
0
1
1
1
0
1
0
0
2
0
1
0
1
2
0
1
1
0
2
0
1
1
1
2
1
0
0
0
3
1
0
0
1
3
1
0
1
0
3
1
0
1
1
3
1
1
0
0
4
1
1
0
1
4
1
1
1
0
4
1
1
1
1
4
Table 8.9 [0] Digital input
If
[1] Serial communication
is selected, activate commands
only when given via serial communication.
Terminal
Bit 00/01, 13/14 Function
Msb
Lsb
Msb
Lsb
Preset ref., Set-up no.
0
0
0
0
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
1
0
1
0
1
2
0
1
1
0
3
0
1
1
1
4
1
0
0
0
1
1
0
0
1
2
1
0
1
0
3
1
0
1
1
4
1
1
0
0
1
1
1
0
1
2
1
1
1
0
3
1
1
1
1
4
Table 8.10 [1] Serial communication
If
[2] Logic AND
is selected, activate both signals to perform
the function.
Troubleshooting
Programming Guide
MG37G102
Danfoss A/S © Rev. 05/2014 All rights reserved.
49
8