Bit
Bit value=0
Bit value=1
Bit value
00
Control not ready
Control ready
1
7
01
Drive not ready
Drive ready
1
02
Coasting
Enable
1
03
No error
Trip
0
04
No error
Error (no trip)
0
0
05
Reserved
-
0
06
No error
Triplock
0
07
No warning
Warning
0
08
Speed reference
Speed = reference
1
F
09
Local operation
Bus control
1
10
Outside frequency range
Within frequency range
1
11
No operation
In operation
1
12
Drive OK
Stopped, autostart
0
0
13
Voltage OK
Voltage exceeded
0
14
Torque OK
Torque exceeded
0
15
Timers OK
Timers exceeded
0
Function active
Function inactive
Table 7.6 Active Bit Functions for Status Word Telegram using PPO Type
7.4 Example 4: PLC Programming
In this example PPO type 6 is placed in the input/output address, see
and
Illustration 7.2 FC 302 and PPO Type 6 PCD
Input
address
256-257
258-259
260-261
262-263
Output
address
256-257
258-259
260-261
262-263
Set-up
Status
word
MAV
Motor
torque
Digital
input
Set-up
Control
word
Reference
Not used
Not used
Table 7.7 Input/Output Address Set-up
This network sends a start command (047C hex) and a
reference (2000 hex) of 50% to the frequency converter.
Illustration 7.3 Network Sends a Start Command and a
Reference of 50% to the Frequency Converter.
Application Examples
Programming Guide
46