3.5.2 Mounting in a VLT
®
DriveMotor FCP
106 Frequency Converter
1.
Remove the lid from the frequency converter.
2.
Check whether the fieldbus option is already
mounted in the frequency converter. If already
mounted, go to step 4. If not mounted, go to
step 3.
3.
Mount the fieldbus option.
4.
Set the termination switch (shown in
Illustration 3.7
) on the fieldbus option to ON,
when the frequency converter is the last station
on the segment.
195NA499.10
1
4
2
3
1
Lid
2
VLT
®
PROFIBUS DP MCA 101 option card
3
Connector plug
4
FCP 106
Illustration 3.5 Exploded View
195NA498.10
Illustration 3.6 Option Mounted in FCP 106
3.6 Setting Address Switches
Set the address switches to give the option a unique ID.
Select an address range from 0–125 (factory setting 127)
according to
Table 3.1
.
Switch
8
7
6
5
4
3
2
1
Address
value
Not
used
+64 +32 +16
+8
+4
+2
+1
5
Not
used
OFF OFF OFF OFF ON
OFF
ON
35
Not
used
OFF
ON OFF OFF OFF
ON
ON
82
Not
used
ON
OFF ON OFF OFF
ON
OFF
Table 3.1 Settings for the Address Switches
Alternatively, assign a unique ID from
parameter 9-18 Node
Address
. For setting the address from
parameter 9-18 Node
Address
, ensure that all address switches are set to ON.
When the address is already set using address hardware
switches, the address value shown in
parameter 9-18 Node
Address
is read-only.
Installation
VLT
®
PROFIBUS DP MCA 101
8
Danfoss A/S © 07/2015 All rights reserved.
MG33C602
3
3