6.2 Ordering Numbers: Brake Resistors
Danfoss offers a wide variety of different resistors that are specially designed for our frequency converters. See
chapter 2.9.4 Control with Brake Function
for the dimensioning of brake resistors. This section lists the ordering numbers for
the brake resistors.
6.2.1 Ordering Numbers: Brake Resistors 10%
FC 280
P
m (HO)
R
min
R
br. nom
R
rec
P
br avg
Ordering
number
Period
Cable
cross-
section
1)
Thermal
relay
Maximum
brake torque
with R
rec
T4
[kW (hp)]
[
Ω
]
[
Ω
]
[
Ω
]
[kW (hp)]
175Uxxxx
[s]
[mm
2
(AWG)]
[A]
[%]
PK37
0.37 (0.5)
890
1041.98
989
0.030
(0.04)
3000
120
1.5 (16)
0.3
139
PK55
0.55 (0.75)
593
693.79
659
0.045
(0.06)
3001
120
1.5 (16)
0.4
131
PK75
0.75 (1.0)
434
508.78
483
0.061
(0.08)
3002
120
1.5 (16)
0.4
129
P1K1
1.1 (1.5)
288
338.05
321
0.092
(0.12)
3004
120
1.5 (16)
0.5
132
P1K5
1.5 (2.0)
208
244.41
232
0.128
(0.172)
3007
120
1.5 (16)
0.8
145
P2K2
2.2 (3.0)
139
163.95
155
0.190
(0.255)
3008
120
1.5 (16)
0.9
131
P3K0
3 (4.0)
100
118.86
112
0.262
(0.351)
3300
120
1.5 (16)
1.3
131
P4K0
4 (5.0)
74
87.93
83
0.354
(0.475)
3335
120
1.5 (16)
1.9
128
P5K5
5.5 (7.5)
54
63.33
60
0.492
(0.666)
3336
120
1.5 (16)
2.5
127
P7K5
7.5 (10)
38
46.05
43
0.677
(0.894)
3337
120
1.5 (16)
3.3
132
P11K
11 (15)
27
32.99
31
0.945
(1.267)
3338
120
1.5 (16)
5.2
130
P15K
15 (20)
19
24.02
22
1.297
(1.739)
3339
120
1.5 (16)
6.7
129
P18K
18.5 (25)
16
19.36
18
1.610
(2.158)
3340
120
1.5 (16)
8.3
132
P22K
22 (30)
16
18.00
17
1.923
(2.578)
3357
120
1.5 (16)
10.1
128
Table 6.2 FC 280 - Mains: 380–480 V (T4), 10% Duty Cycle