2.2.2 AC Mains Connection
•
Size the wiring based on the input current of the
frequency converter. For maximum wire sizes, see
chapter 7.1 Power-dependent Specifications
•
Comply with local and national electrical codes
for cable sizes.
Procedure
1.
Connect the AC input power cables to terminals
N and L for single-phase units (see
), or to terminals L1, L2, and L3 for
3-phase units (see
and
2.
Depending on the configuration of the
equipment, connect the input power to the
mains input terminals or the input disconnect.
3.
Ground the cable in accordance with the
grounding instructions in
chapter Grounding
in
the
VLT
®
Midi Drive FC 280 Operating Guide
.
4.
When supplied from an isolated mains source (IT
mains or floating delta) or TT/TN-S mains with a
grounded leg (grounded delta), ensure that the
RFI filter screw is removed. Removing the RFI
screw prevents damage to the DC link and
reduces ground capacity currents in accordance
with IEC 61800-3.