7 Specifications
7.1 Mains Supply 1x200–240 V AC
Table 12: Mains Supply 1x200–240 V AC
Normal overload 150% for 1 minute
Drive
PK18
PK37
PK75
P1K5
P2K2
Typical shaft output [kW]
0.18
0.37
0.75
1.5
2.2
Typical shaft output [hp]
0.25
0.5
1
2
3
Enclosure protection rating IP20
M1
M1
M1
M2
M3
Output current
Continuous (3x200–240 V AC) [A]
1.2
2.2
4.2
6.8
9.6
Intermittent (3x200–240 V AC) [A]
1.8
3.3
6.3
10.2
14.4
Maximum cable size
(Mains, motor) [mm
2
/AWG]
4/10
Maximum input current
Continuous (1x200–240 V) [A]
3.3
6.1
11.6
18.7
26.4
Intermittent (1x200–240 V) [A]
4.5
8.3
15.6
26.4
37
Maximum mains fuses [A]
See
chapter Fuses
.
Environment
Estimated power loss [W],
Best case/typical
(1)
12.5/
15.5
20/
25
36.5/
44
61/
67
81/
85.1
Weight enclosure IP20 [kg]
1.0
1.0
1.0
1.5
2.8
Efficiency [%],
Best case/typical
(2)
95.6/
94.5
96.5/
95.6
96.6/
96
97/
96.7
96.9/
97.1
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to Danfoss
website.
2
Efficiency measured at nominal current. For energy efficiency class, see chapter Surroundings. For part load losses, see Danfoss
website.
7.2 Mains Supply 3x380–480 V AC
Table 13: Mains Supply 3x380–480 V AC
Normal overload 150% for 1 minute
Drive
PK37
PK75
P1K5
P2K2
P3K0
P4K0
Typical shaft output [kW]
0.37
0.75
1.5
2.2
3.0
4.0
Typical shaft output [hp]
0.5
1
2
3
4
5.5
Enclosure protection rating IP20
M1
M1
M1/M2
M2
M3
M3
Output current
AQ348848915086en-000101 / 130R0943
26 | Danfoss A/S © 2020.09
Specifications
VLT® Micro Drive FC 51
Operating Guide