3.1.2 How to Install Option in Frequency Converter
Items required for installing a fieldbus option in the frequency converter:
-
The fieldbus option
-
Fieldbus option adaptor frame for the FC 200/FC 300. This frame is deeper than the standard frame, to allow space for the fieldbus option
beneath
-
Strain relief (only for A1 and A2 enclosures)
Instructions:
-
Remove LCP panel from the FC 200/FC 300.
-
Remove the frame located beneath and discard it.
-
Push the option into place. The Ethernet connectors must be facing upwards.
-
Remove both knock-outs on the fieldbus option adaptor frame.
-
Push the fieldbus option adaptor frame for the FC 200/FC 300 into place.
-
Replace the LCP and attach cable
NB!
Do not strip the Ethernet cable and ground it via the strain relief-plate! The grounding of screened Ethernet cable is done through the
RJ-45 connector on the option.
NB!
After installing the MCA 121 option, be aware of the following parameter settings:
par. 8-01
Control Site
: [2]
Controlword only
or [0]
Digital and ctrl. word
: [3]
Option A
3 How to Install
MCA 121 EtherNet/IP
8
MG.90.J2.02 - VLT
®
is a registered Danfoss trademark
3
Summary of Contents for VLT MCA 121 EtherNet/IP
Page 14: ...4 How to Configure MCA 121 EtherNet IP 14 MG 90 J2 02 VLT is a registered Danfoss trademark 4...
Page 20: ...5 How to Control MCA 121 EtherNet IP 20 MG 90 J2 02 VLT is a registered Danfoss trademark 5...
Page 50: ...8 Appendix MCA 121 EtherNet IP 50 MG 90 J2 02 VLT is a registered Danfoss trademark 8...