[0]
Port 1
[1]
Port 2
12-10 Link Status
Option:
Function:
Read only. Displays the link status of the Ethernet ports.
[0]
No link
[1]
Link
12-11 Link Duration
Option:
Function:
Link Duration Port 1 (dd:hh:mm:ss) Read only. Displays the duration of the present link on each port in dd:hh:mm:ss.
12-12 Auto Negotiation
Option:
Function:
Configures Auto Negotiation of Ethernet link parameters, for each port: ON or OFF.
[0]
Off
Link Speed
and
Link Duplex
can be configured in par. 12-13 and 12-14.
[1]
On
12-13 Link Speed
Option:
Function:
Forces the link speed for each port in 10 or 100 Mbps. If par. 12-12 is set to: ON, this parameter is
read only and displays the actual link speed. “None” is displayed if no link is present.
[0] *
None
[1]
10 Mbps
[2]
100 Mbps
12-14 Link Duplex
Option:
Function:
Forces the duplex for each port to Full or Half duplex. If par. 12-12 is set to: ON, this parameter is
read only.
[0]
Half duplex
[1] *
Full duplex
6.2.3 Process Data
12-20 Control Instance
Range:
Function:
[None, 20, 21, 100, 101, 103]
Read only. Displays the originator-to-target connection point. If no CIP connection is present “None”
is displayed.
12-21 Process Data Config Write
Range:
Function:
[[0 - 9] PCD read 0 - 9]
Configuration of readable process data.
NB!
For configuration of 2-word (32-bit) parameter read/write, use 2 consecutive arrays in par. 12-21 and 12-22.
MCA 121 EtherNet/IP
6 Parameters
MG.90.J2.02 - VLT
®
is a registered Danfoss trademark
37
6