[3] *
Logic OR
Activates the Reverse command via the fieldbus/serial communication port OR via one of the digital
inputs.
NB!
This parameter is only active when par. 8-01
Control Site
is set to [0]
Digital and control word
.
8-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via
the fieldbus.
[0]
Digital input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial communication port or fieldbus option.
[2]
Logic AND
Activates the set-up selection via the fieldbus/serial communication port, AND additionally via one
of the digital inputs.
[3] *
Logic OR
Activate the set-up selection via the fieldbus/serial communication port OR via one of the digital
inputs.
NB!
This parameter is active only when par.8-01
is set to [0]
Digital and control word
.
8-56 Preset Reference Select
Option:
Function:
Select control of the frequency converter Preset Reference selection via the terminals (digital input)
and/or via the fieldbus.
[0]
Digital input
Activates Preset Reference selection via a digital input.
[1]
Bus
Activates Preset Reference selection via the serial communication port or fieldbus option.
[2]
Logic AND
Activates Preset Reference selection via the fieldbus/serial communication port, AND additionally
via one of the digital inputs.
[3] *
Logic OR
Activates the Preset Reference selection via the fieldbus/serial communication port OR via one of
the digital inputs.
NB!
This parameter is active only when par.8-01
is set to [0]
Digital and control word
.
6.2 Parameter Group 12-**
6.2.1 IP Settings
12-00 IP Address Assignment
Option:
Function:
Selects the IP Address assignment method.
[0] *
Manual
IP-address can be set in par. 12-01 IP Address.
[1]
DHCP
IP-address is assigned via DHCP server.
[2]
BOOTP
IP-address is assigned via BOOTP server.
MCA 121 EtherNet/IP
6 Parameters
MG.90.J2.02 - VLT
®
is a registered Danfoss trademark
35
6