6.4.2 Digital In/Out 5-**
Par.
No. #
Parameter description
Default value
(SR = Size related)
4 set-up
FC 302
only
Change dur-
ing opera-
tion
Conver-
sion index
Type
5-0* Digital I/O mode
5-00
Digital I/O Mode
[0] PNP
All set-ups
FALSE
-
Uint8
5-01
Terminal 27 Mode
[0] Input
All set-ups
TRUE
-
Uint8
5-02
Terminal 29 Mode
[0] Input
All set-ups
x
TRUE
-
Uint8
5-1* Digital Inputs
5-10
Terminal 18 Digital Input
[8] Start
All set-ups
TRUE
-
Uint8
5-11
Terminal 19 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-12
Terminal 27 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-13
Terminal 29 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-14
Terminal 32 Digital Input
[90] AC Contactor
All set-ups
TRUE
-
Uint8
5-15
Terminal 33 Digital Input
[91] DC Contactor
All set-ups
TRUE
-
Uint8
5-16
Terminal X30/2 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-17
Terminal X30/3 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-18
Terminal X30/4 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-19
Terminal 37 Safe Stop
[1] Safe Stop Alarm
1 set-up
TRUE
-
Uint8
5-20
Terminal X46/1 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-21
Terminal X46/3 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-22
Terminal X46/5 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-23
Terminal X46/7 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-24
Terminal X46/9 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-25
Terminal X46/11 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-26
Terminal X46/13 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-3* Digital Outputs
5-30
Terminal 27 Digital Output
[0] No operation
All set-ups
TRUE
-
Uint8
5-31
Terminal 29 Digital Output
[0] No operation
All set-ups
x
TRUE
-
Uint8
5-32
Term X30/6 Digi Out (MCB 101)
[0] No operation
All set-ups
TRUE
-
Uint8
5-33
Term X30/7 Digi Out (MCB 101)
[0] No operation
All set-ups
TRUE
-
Uint8
5-4* Relays
5-40
Function Relay
[0] No operation
All set-ups
TRUE
-
Uint8
5-41
On Delay, Relay
0.30 s
All set-ups
TRUE
-2
Uint16
5-42
Off Delay, Relay
0.30 s
All set-ups
TRUE
-2
Uint16
6.4.3 Comm. and Options 8-**
Par.
No. #
Parameter description
Default value
(SR = Size related)
4 set-up
FC 302
only
Change dur-
ing opera-
tion
Conver-
sion index
Type
8-0* General Settings
8-01
Control Site
[0] Digital and ctrl.word
All set-ups
TRUE
-
Uint8
8-02
Control Word Source
null
All set-ups
TRUE
-
Uint8
8-03
Control Word Timeout Time
1.0 s
1 set-up
TRUE
-1
Uint32
8-04
Control Word Timeout Function
[0] Off
1 set-up
TRUE
-
Uint8
8-05
End-of-Timeout Function
[1] Resume set-up
1 set-up
TRUE
-
Uint8
8-06
Reset Control Word Timeout
[0] Do not reset
All set-ups
TRUE
-
Uint8
8-3* FC Port Settings
8-30
Protocol
[1] FC MC
1 set-up
TRUE
-
Uint8
8-31
Address
2 N/A
1 set-up
TRUE
0
Uint8
8-32
FC Port Baud Rate
[2] 9600 Baud
1 set-up
TRUE
-
Uint8
8-35
Minimum Response Delay
10 ms
All set-ups
TRUE
-3
Uint16
8-36
Max Response Delay
5000 ms
1 set-up
TRUE
-3
Uint16
8-37
Max Inter-Char Delay
25 ms
1 set-up
TRUE
-3
Uint16
8-5* Digital/Bus
8-53
Start Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-55
Set-up Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
6 How to Program the Low Harmonic Drive
VLT HVAC Low Harmonic Drive Instruction
Manual
6-64
MG.16.A1.22 - VLT
®
is a registered Danfoss trademark