4.3.10 IP21 Drip Shield Installation (Frame size D)
To comply with the IP21 rating, a separate drip shield is to be
installed as explained below:
•
Remove the two front screws.
•
Insert the drip shield and replace the screws.
•
Torque the screws to 5.6 Nm (50 in-lbs).
NOTE!
Drip shield is necessary on both filter and drive section.
Figure 4.26: Install the drip shield.
↓
↓
VLT HVAC Low Harmonic Drive Instruction
Manual
4 How to Install
MG.16.A1.22 - VLT
®
is a registered Danfoss trademark
4-29