Line Power Supply 3 x 380–480 V AC
P500
P560
P630
P710
P800
P1M0
Typical shaft output at 400 V [kW]
500
560
630
710
800
1000
Typical shaft output at 460 V [hp]
650
750
900
1000
1200
1350
Enclosure protection rating IP21,
IP54 without/with options cabinet
F1/F3
F1/F3
F1/F3
F1/F3
F2/F4
F2/F4
Output current
Continuous (at 400 V) [A]
880
990
1120
1260
1460
1720
Intermittent (60 s overload)
(at 400 V) [A]
968
1089
1232
1386
1606
1892
Continuous (at 460/480 V) [A]
780
890
1050
1160
1380
1530
Intermittent (60 s overload)
(at 460/480 V) [A]
858
979
1155
1276
1518
1683
Continuous KVA (at 400 V) [KVA]
610
686
776
873
1012
1192
Continuous KVA (at 460 V) [KVA]
621
709
837
924
1100
1219
Maximum input current
Continuous
(at 400 V) [A]
857
964
1090
1227
1422
1675
Continuous (at 460/480 V) [A]
759
867
1022
1129
1344
1490
Maximum cable size, motor [mm
2
(AWG
2)
)]
8 x 150
(8 x 300 mcm)
12 x 150
(12 x 300 mcm)
Maximum cable size, line power
F1/F2 [mm
2
(AWG
2)
)]
8 x 240
(8 x 500 mcm)
Maximum cable size, line power
F3/F4 [mm
2
(AWG
2)
)]
8 x 456
(8 x 900 mcm)
Maximum cable size, load sharing
[mm
2
(AWG
2)
)]
4 x 120
(4 x 250 mcm)
Maximum cable size, brake [mm
2
(AWG
2)
)
4 x 185
(4 x 350 mcm)
6 x 185
(6 x 350 mcm)
Maximum external pre-fuses [A]
1)
1600
2000
2500
Estimated power loss at rated
maximum load [W]
3)
, 400 V, F1 &
F2
10162
11822
12512
14674
17293
19278
Estimated power loss at rated
maximum load [W]
3)
, 460 V, F1 &
F2
8876
10424
11595
13213
16229
16624
Maximum added losses of A1 RFI,
circuit breaker or disconnect, &
contactor, F3 & F4
963
1054
1093
1230
2280
2541
Maximum panel options losses
400
Weight,
enclosure protection rating IP21,
IP54 [kg (lb)]
1017/1318 (2242.1/2905.7)
1260/1561 (2778/3441.5)
Weight rectifier module [kg (lb)]
102 (224.9)
136 (300)
Weight inverter module [kg (lb)]
102 (224.9)
136 (300)
102 (224.9)
Efficiency
4)
0.98
Output frequency
0–590 Hz
Heatsink overtemperature trip
95
°
C (203 °F)
Power card ambient trip
85
°
C (185 °F)
Table 7.2 Line Power Supply 3 x 380–480 V AC