Group
Title
Function
24-**
Application Functions 2
Parameters used to set up fire mode and/or to control a bypass contactor/starter if designed into
the system.
25-**
Cascade Controller
Parameters used to configure and monitor the built-in pump cascade controller (typically used
for pump booster sets).
26-**
Analog I/O Option MCB
109
Parameters used to configure the analog I/O option (MCB 109) including:
•
Definition of the analog input types (for example, voltage, Pt1000 or Ni1000).
•
Scaling and definition of the analog output functions and scaling.
Table 6.1 Parameter Groups
Parameter descriptions and selections are displayed on the
graphic (GLCP) or numeric (NLCP) display. (See the relevant
section for details.) Access the parameters by pressing
[Quick Menu] or [Main Menu] on the LCP. The
Quick Menu
is used primarily for commissioning the unit at start-up by
providing the parameters necessary to start operation. The
Main Menu
provides access to all parameters for detailed
application programming.
All digital input/output and analog input/output terminals
are multifunctional. All terminals have factory default
functions suitable for most HVAC applications but if other
special functions are required, they must be programmed
as explained in parameter group
5-** Digital In/out
or
6-**
Analog In/out
.
6.1.2 Quick Menu Mode
Parameter data
The graphical display (GLCP) provides access to all
parameters listed in the
Quick Menu
. The numeric display
(NLCP) only provides access to the
Quick Set-up
parameters.
To set parameters pressing [Quick Menu] - enter or change
parameter data or settings in accordance with the
following procedure:
1.
Press [Quick Menu].
2.
Press [
▲
] or [
▼
] to find the parameter to change.
3.
Press [OK].
4.
Press [
▲
] or [
▼
] to select the correct parameter
setting.
5.
Press [OK].
6.
To move to a different digit within a parameter
setting, use the [
◀
] and [
▶
].
7.
Highlighted area indicates digit selected for
change.
8.
Press [Cancel] to disregard change, or press [OK]
to accept change and enter the new setting.
Example of changing parameter data
Assume
parameter 22-60 Broken Belt Function
is set to
[0]
Off
. To monitor the fan-belt condition, non-broken or
broken, follow this procedure:
1.
Press [Quick Menu].
2.
Press [
▼
] to select
Function Set-ups
.
3.
Press [OK].
4.
Press [
▼
] to select
Application Settings
.
5.
Press [OK].
6.
Press [OK] again for
Fan Functions
.
7.
Press [OK] to select
Broken Belt Function
.
8.
Press [
▼
] to select
[2] Trip
.
If a broken fan-belt is detected, the adjustable frequency
drive trips.
Select
Q1 My Personal Menu
to display personal
parameters
For example, an AHU or pump OEM may have pre-
programmed personal parameters to be in
My Personal
Menu
during factory commissioning to make on-site
commissioning/fine-tuning simpler. These parameters are
selected in
parameter 0-25 My Personal Menu
. Up to 20
different parameters can be programmed in this menu.
Select
Changes Made
to obtain information about:
•
The last 10 changes. Press [
▲
] and [
▼
] to scroll
between the last 10 changed parameters.
•
The changes made since default setting.
Loggings
Loggings
show information about the display line
readouts. The information is shown as graphs.
Only display parameters selected in
parameter 0-20 Display
Line 1.1 Small
and
parameter 0-24 Display Line 3 Large
can
be viewed. Up to 120 samples can be stored in the
memory for later reference.
Quick Set-up
Efficient parameter set-up for HVAC applications
The parameters can easily be set up for most HVAC
applications only by using the
Quick Set-up
.
How to Program
VLT
®
HVAC Drive FC 102
78
Danfoss A/S © 08/2014 All rights reserved.