Parameter
Range
Default
Function
1-24 Motor Current
0.01-10000.00 A
Size related
Enter motor current from nameplate data
1-25 Motor Nominal
Speed
100.0-9999.0 RPM
Size related
Enter motor nominal speed from nameplate data
1-26 Motor Cont. Rated
Torque
0.1-1000.0
Size related
This parameter is available only when
1-10 Motor
Construction
Design is set to
[1] PM, non-salient
SPM
.
NOTICE
Changing this parameter affects
settings of other parameters
1-29 Automatic Motor
Adaption (AMA)
See 1-29 Automatic Motor
Adaption (AMA)
Off
Performing an AMA optimises motor performance
1-30 Stator Resistance
(Rs)
0.000-99.990
Size related
Set the stator resistance value
1-37 d-axis Inductance
(Ld)
0-1000
Size related
Enter the value of the d-axis inductance.
Obtain the value from the permanent magnet
motor data sheet. The de-axis inductance cannot
be found by performing an AMA.
1-39 Motor Poles
2-100
4
Enter the number of motor poles
1-40 Back EMF at 1000
RPM
10-9000
Size related
Line-Line RMS back EMF voltage at 1000 RPM
1-73 Flying Start
When PM is selected, Flying Start is enabled and
can not disable
1-73 Flying Start
[0] Disabled
[1] Enabled
0
Select
[1] Enable
to enable the frequency converter
to catch a motor spinning due to mains drop-out.
Select
[0] Disable
if this function is not required.
When is enabled
1-71 Start Delay
and
1-72 Start
Function
have no function. is active in VVC
plus
mode only
3-02 Minimum Reference -4999-4999
0
The minimum reference is the lowest value
obtainable by summing all references
3-03 Maximum Reference -4999-4999
50
The maximum reference is the lowest obtainable
by summing all references
3-41 Ramp 1 Ramp Up
Time
0.05-3600.0 s
Size related
Ramp up time from 0 to rated
1-23 Motor
Frequency
if Asynchron motor is selected; ramp up
time from 0 to
1-25 Motor Nominal Speed
if PM
motor is selected
3-42 Ramp 1 Ramp
Down Time
0.05-3600.0 s
Size related
Ramp down time from rated
1-23 Motor Frequency
to 0 if Asynchron motor is selected; ramp down
time from
1-25 Motor Nominal Speed
to 0 if PM
motor is selected
4-12 Motor Speed Low
Limit [Hz]
0.0-400 Hz
0 Hz
Enter the minimum limit for low speed
4-14 Motor Speed High
Limit [Hz]
0.0-400 Hz
65 Hz
Enter the maximum limit for high speed
4-19 Max Output
Frequency
0-400
Size related
Enter the maximum output frequency value
5-40 Function Relay [0]
Function relay
See 5-40 Function Relay
Alarm
Select the function to control output relay 1
5-40 Function Relay [1]
Function relay
See 5-40 Function Relay
Drive running
Select the function to control output relay 2
6-10 Terminal 53 Low
Voltage
0-10 V
0.07 V
Enter the voltage that corresponds to the low
reference value
How to Programme
VLT
®
HVAC Basic Drive FC 101 Design Guide
72
MG18C502 - Rev. 2013-09-06