Frequency converter
P18K
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Typical shaft output [kW]
18.5
22.0
30.0
37.0
45.0
55.0
75.0
90.0
Typical shaft output [hp]
25.0
30.0
40.0
50.0
60.0
70.0
100.0
125.0
IP20 frame
H5
H5
H6
H6
H6
H7
H7
H8
Max. cable size in terminals
(mains, motor) [mm
2
/AWG]
16/6
16/6
35/2
35/2
35/2
50/1
95/0
120/250MC
M
Output current - 40
°
C ambient temperature
Continuous (3x380-440 V)[A]
37.0
42.5
61.0
73.0
90.0
106.0
147.0
177.0
Intermittent (3x380-440 V) [A]
40.7
46.8
67.1
80.3
99.0
116.0
161.0
194.0
Continuous (3x440-480 V) [A]
34.0
40.0
52.0
65.0
80.0
105.0
130.0
160.0
Intermittent (3x440-480 V) [A]
37.4
44.0
57.2
71.5
88.0
115.0
143.0
176.0
Max. input current
Continuous (3x380-440 V) [A]
35.2
41.5
57.0
70.0
84.0
103.0
140.0
166.0
Intermittent (3x380-440 V) [A]
38.7
45.7
62.7
77.0
92.4
113.0
154.0
182.0
Continuous (3x440-480 V) [A]
29.3
34.6
49.2
60.6
72.5
88.6
120.9
142.7
Intermittent (3x440-480 V) [A]
32.2
38.1
54.1
66.7
79.8
97.5
132.9
157.0
Max. mains fuses
Estimated power loss [W],
best case/typical
1)
412/456
475/523
733
922
1067
1133
1733
2141
Weight enclosure IP20 [kg]
9.5
9.5
24.5
24.5
24.5
36.0
36.0
51.0
Efficiency [%], best case/typical
1)
98.1/97.9
98.1/97.9
97.8
97.7
98
98.2
97.8
97.9
Output current - 50
°
C ambient temperature
Continuous (3x380-440 V) [A]
34.1
38.0
48.8
58.4
72.0
74.2
102.9
123.9
Intermittent (3x380-440 V) [A]
37.5
41.8
53.7
64.2
79.2
81.6
113.2
136.3
Continuous (3x440-480 V) [A]
31.3
35.0
41.6
52.0
64.0
73.5
91.0
112.0
Intermittent (3x440-480 V) [A]
34.4
38.5
45.8
57.2
70.4
80.9
100.1
123.2
Table 8.3 3x380-480 V AC, P18K-P90K, H5-H8
1) At rated load conditions
General Specifications and ...
VLT
®
HVAC Basic Drive FC 101 Design Guide
100
MG18C502 - Rev. 2013-09-06
8