8.1.4 Mains Supply 3x525-600 V AC
Frequency converter
P2K2 P3K0 P3K7 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
Typical shaft output [kW]
2.2
3.0
3.7
5.5
7.5
11.0
15.0
18.5
22.0
30.0
37
45.0
55.0
75.0
90.0
Typical shaft output [hp]
3.0
4.0
5.0
7.5
10.0
15.0
20.0
25.0
30.0
40.0
50.0
60.0
70.0 100.0 125.0
IP20 frame
H9
H9
H9
H9
H9
H10
H10
H6
H6
H6
H7
H7
H7
H8
H8
Max. cable size in terminals
(mains, motor) [mm
2
/AWG]
4/10
4/10
4/10
4/10
4/10
10/8
10/8
35/2 35/2 35/2 50/1 50/1 50/1 95/0 120/
(4/0)
Output current - 40
°
C ambient temperature
Continuous (3x525-550 V) [A]
4.1
5.2
6.4
9.5
11.5
19.0
23.0
28.0
36.0
43.0
54.0
65.0
87.0 105.0 137.0
Intermittent (3x525-550 V) [A]
4.5
5.7
7.0
10.5
12.7
20.9
25.3
30.8
39.6
47.3
59.4
71.5
95.7 115.5 150.7
Continuous (3x551-600 V) [A]
3.9
4.9
6.1
9.0
11.0
18.0
22.0
27.0
34.0
41.0
52.0
62.0
83.0 100.0 131.0
Intermittent (3x551-600 V) [A]
4.3
5.4
6.7
9.9
12.1
19.8
24.2
29.7
37.4
45.1
57.2
68.2
91.3 110.0 144.1
Max. input current
Continuous (3x525-550 V) [A]
3.7
5.1
5.0
8.7
11.9
16.5
22.5
27.0
33.1
45.1
54.7
66.5
81.3 109.0 130.9
Intermittent (3x525-550 V) [A]
4.1
5.6
6.5
9.6
13.1
18.2
24.8
29.7
36.4
49.6
60.1
73.1
89.4 119.9 143.9
Continuous (3x551-600 V) [A]
3.5
4.8
5.6
8.3
11.4
15.7
21.4
25.7
31.5
42.9
52.0
63.3
77.4 103.8 124.5
Intermittent (3x551-600 V) [A]
3.9
5.3
6.2
9.2
12.5
17.3
23.6
28.3
34.6
47.2
57.2
69.6
85.1 114.2 137.0
Max. mains fuses
See
5.2.3 Fuses and Circuit Breakers
Estimated power loss [W],
best case/typical
1)
65
90
110
132
180
216
294
385
458
542
597
727
1092 1380 1658
Weight enclosure IP54 [kg]
6.6
6.6
6.6
6.6
6.6
11.5
11.5
24.5
24.5
24.5
36.0
36.0
36.0
51.0
51.0
Efficiency [%],
best case/typical
1)
97.9
97
97.9
98.1
98.1
98.4
98.4
98.4
98.4
98.5
98.5
98.7
98.5
98.5
98.5
Output current - 50
°
C ambient temperature
Continuous (3x525-550 V) [A]
2.9
3.6
4.5
6.7
8.1
13.3
16.1
19.6
25.2
30.1
37.8
45.5
60.9
73.5
95.9
Intermittent (3x525-550 V) [A]
3.2
4.0
4.9
7.4
8.9
14.6
17.7
21.6
27.7
33.1
41.6
50.0
67.0
80.9 105.5
Continuous (3x551-600 V) [A]
2.7
3.4
4.3
6.3
7.7
12.6
15.4
18.9
23.8
28.7
36.4
43.3
58.1
70.0
91.7
Intermittent (3x551-600 V) [A]
3.0
3.7
4.7
6.9
8.5
13.9
16.9
20.8
26.2
31.6
40.0
47.7
63.9
77.0 100.9
Table 8.8 3x525-600 V AC, P2K2-P90K, H6-H10
1) At rated load conditions
General Specifications and ...