![Danfoss VLT HVAC Basic Drive FC 101 Design Manual Download Page 49](http://html1.mh-extra.com/html/danfoss/vlt-hvac-basic-drive-fc-101/vlt-hvac-basic-drive-fc-101_design-manual_3680316049.webp)
4.2.2 Harmonic Filters
3x380-480 V 50 Hz
Power
[kW]
Drive input
current
Continuous
[A]
Default
switching
frequency
[kHz]
THID
level
[%]
Order
number
filter IP00
Code
number
filter IP20
22
41.5
4
4
130B1397 130B1239
30
57
4
3
130B1398 130B1240
37
70
4
3
130B1442 130B1247
45
84
3
3
130B1442 130B1247
55
103
3
5
130B1444 130B1249
75
140
3
4
130B1445 130B1250
90
176
3
4
130B1445 130B1250
Table 4.3 AHF Filters (5% current distortion)
3x380-480 V 50 Hz
Power
[kW]
Drive input
current
Continuous
[A]
Default
switching
frequency
[kHz]
THID
level
[%]
Order
number
filter IP00
Code
number
filter IP20
22
41.5
4
6
130B1274 130B1111
30
57
4
6
130B1275 130B1176
37
70
4
9
130B1291 130B1201
45
84
3
9
130B1291 130B1201
55
103
3
9
130B1292 130B1204
75
140
3
8
130B1294 130B1213
90
176
3
8
130B1294 130B1213
Table 4.4 AHF Filters (10% current distortion)
3x440-480 V 60 Hz
Power
[kW]
Drive input
current
Continuous
[A]
Default
switching
frequency
[kHz]
THID
level
[%]
Order
number
filter IP00
Code
number
filter IP20
22
34.6
4
3
130B1792 130B1757
30
49
4
3
130B1793 130B1758
37
61
4
3
130B1794 130B1759
45
73
3
4
130B1795 130B1760
55
89
3
4
130B1796 130B1761
75
121
3
5
130B1797 130B1762
90
143
3
5
130B1798 130B1763
Table 4.5 AHF Filters (5% current distortion)
3x440-480 V 60 Hz
Power
[kW]
Drive input
current
Continuous
[A]
Default
switching
frequency
[kHz]
THID
level
[%]
Order
number
filter IP00
Code
number
filter IP20
22
34.6
4
6
130B1775 130B1487
30
49
4
8
130B1776 130B1488
37
61
4
7
130B1777 130B1491
45
73
3
9
130B1778 130B1492
55
89
3
8
130B1779 130B1493
75
121
3
9
130B1780 130B1494
90
143
3
10
130B1781 130B1495
Table 4.6 AHF Filters (10% current distortion)
How to Order
VLT
®
HVAC Basic Drive FC 101 Design Guide
MG18C502 - Rev. 2013-09-06
47
4
4