7 Specifications
7.1 Electrical Data
7.1.1 Mains Supply 3x200–240 V AC
Type designation
P1K1
P1K5
P2K2
P3K0
P3K7
Overload
1)
NO
NO
NO
NO
NO
Typical shaft output [kW]
1.1
1.5
2.2
3.0
3.7
Typical shaft output [hp] at 208 V
1.5
2.0
2.9
4.0
4.9
IP20/chassis
6)
A2
A2
A2
A3
A3
IP55/NEMA 12
A4/A5
A4/A5
A4/A5
A5
A5
IP66/NEMA 4X
A4/A5
A4/A5
A4/A5
A5
A5
Output current
Continuous (3x200–240 V) [A]
6.6
7.5
10.6
12.5
16.7
Intermittent (3x200–240 V) [A]
7.3
8.3
11.7
13.8
18.4
Continuous kVA (208 V AC) [kVA]
2.38
2.70
3.82
4.50
6.00
Maximum input current
Continuous (3x200–240 V) [A]
5.9
6.8
9.5
11.3
15.0
Intermittent (3x200–240 V) [A]
6.5
7.5
10.5
12.4
16.5
More specifications
Estimated power loss
3)
at rated maximum load [W]
4)
63
82
116
155
185
IP20, IP21 maximum cable cross-section
2)
(mains, motor, brake, and
load sharing) [mm
2
/(AWG)]
4, 4, 4 (12, 12, 12)
(minimum 0.2 (24))
IP55, IP66 maximum cable cross-section
2)
(mains, motor, brake, and
load sharing) [mm
2
/(AWG)]
4, 4, 4 (12, 12, 12)
Maximum cable cross-section with disconnect
6, 4, 4 (10, 12, 12)
Efficiency
5)
0.96
0.96
0.96
0.96
0.96
Table 7.1 Mains Supply 3x200–240 V AC
Specifications
Design Guide
MG16G202
Danfoss A/S © 08/2015 All rights reserved.
115
7
7