8.4 Warning and Alarm Definitions
defines whether a warning is issued before an alarm, and whether the alarm trips the unit or trip locks the unit.
No.
Description
Warning
Alarm/Trip
Alarm/Trip lock
Parameter reference
1
10 Volts low
X
2
Live zero error
(X)
(X)
6-01 Live Zero Timeout
Function
4
Mains phase loss
(X)
(X)
(X)
14-12 Function at Mains
Imbalance
5
DC link voltage high
X
6
DC link voltage low
X
7
DC overvoltage
X
X
8
DC under voltage
X
X
9
Inverter overloaded
X
X
10
Motor ETR overtemperature
(X)
(X)
1-90 Motor Thermal Protection
11
Motor thermistor overtemperature
(X)
(X)
1-90 Motor Thermal Protection
12
Torque limit
X
X
13
Overcurrent
X
X
X
14
Ground fault
X
X
X
15
Hardware mismatch
X
X
16
Short-circuit
X
X
17
Control word timeout
(X)
(X)
8-04 Control Timeout Function
18
Start Failed
23
Internal Fan Fault
X
24
External Fan Fault
X
14-53 Fan Monitor
25
Brake resistor short-circuited
X
26
Brake resistor power limit
(X)
(X)
2-13 Brake Power Monitoring
27
Brake chopper short-circuited
X
X
28
Brake check
(X)
(X)
2-15 Brake Check
29
Drive overtemperature
X
X
X
30
Motor phase U missing
(X)
(X)
(X)
4-58 Missing Motor Phase
Function
31
Motor phase V missing
(X)
(X)
(X)
4-58 Missing Motor Phase
Function
32
Motor phase W missing
(X)
(X)
(X)
4-58 Missing Motor Phase
Function
33
Inrush fault
X
X
34
Fieldbus communication fault
X
X
35
Out of frequency range
X
X
36
Mains Failure
X
X
37
Phase Imbalance
X
X
38
Internal fault
X
X
39
Heatsink sensor
X
X
40
Overload of Digital Output Terminal 27
(X)
5-00 Digital I/O Mode,
5-01 Terminal 27 Mode
41
Overload of Digital Output Terminal 29
(X)
5-00 Digital I/O Mode,
5-02 Terminal 29 Mode
42
Overload of Digital Output On X30/6
(X)
5-32 Term X30/6 Digi Out (MCB
101)
42
Overload of Digital Output On X30/7
(X)
5-33 Term X30/7 Digi Out (MCB
101)
Warnings and Alarms
VLT
®
Refrigeration Drive Instruction Manual
MG16J122 - VLT
®
is a registered Danfoss trademark
8-3