No.
Text
1792
DSP watchdog is active. Debugging of power part
data, motor oriented control data not transferred
correctly.
2049
Power data restarted
2064-2072 H081x: option in slot x has restarted
2080-2088 H082x: option in slot x has issued a power-up wait
2096-2104 H983x: option in slot x has issued a legal power-
up wait
2304
Could not read any data from power EEPROM
2305
Missing SW version from power unit
2314
Missing power unit data from power unit
2315
Missing SW version from power unit
2316
Missint lo_statepage from power unit
2324
Power card configuration is determined to be
incorrect at power-up
2325
A power card has stopped communicating while
main power is applied
2326
Power card configuration is determined to be
incorrect after the delay for power cards to
register.
2327
Too many power card locations have been
registered as present.
2330
Power size information between the power cards
does not match.
2561
No communication from DSP to ATACD
2562
No communication from ATACD to DSP (state
running)
2816
Stack overflow control board module
2817
Scheduler slow tasks
2818
Fast tasks
2819
Parameter thread
2820
LCP stack overflow
2821
Serial port overflow
2822
USB port overflow
2836
cfListMempool too small
3072-5122 Parameter value is outside its limits
5123
Option in slot A: Hardware incompatible with
control board hardware
5124
Option in slot B: Hardware incompatible with
control board hardware.
5125
Option in slot C0: Hardware incompatible with
control board hardware.
5126
Option in slot C1: Hardware incompatible with
control board hardware.
5376-6231 Out of memory
Table 8.4
ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gate drive card, or the ribbon cable between the
power card and gate drive card.
WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove short-
circuit connection. Check
5-00 Digital I/O Mode
and
5-01 Terminal 27 Mode
.
WARNING 41, Overload of digital output terminal 29
Check the load connected to terminal 29 or remove short-
circuit connection. Check
5-00 Digital I/O Mode
and
5-02 Terminal 29 Mode
.
WARNING 42, Overload of digital output on X30/6 or
overload of digital output on X30/7
For X30/6, check the load connected to X30/6 or remove
the short-circuit connection. Check
5-32 Term X30/6 Digi
Out (MCB 101)
.
For X30/7, check the load connected to X30/7 or remove
the short-circuit connection. Check
5-33 Term X30/7 Digi
Out (MCB 101)
.
ALARM 46, Power card supply
The supply on the power card is out of range.
There are three power supplies generated by the switch
mode power supply (SMPS) on the power card: 24 V, 5 V,
±
18 V. When powered with 24 V DC with the MCB 107
option, only the 24 V and 5 V supplies are monitored.
When powered with three phase AC line voltage, all three
supplies are monitored.
WARNING 47, 24 V supply low
The 24 V DC is measured on the control card. The external
24 V DC backup power supply may be overloaded,
otherwise contact the Danfoss supplier.
WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of
allowable limits. The power supply is measured on the
control card. Check for a defective control card. If an
option card is present, check for an overvoltage condition.
WARNING 49, Speed limit
When the speed is not within the specified range in
4-11 Motor Speed Low Limit [RPM]
and
4-13 Motor Speed
High Limit [RPM]
, the adjustable frequency drive shows a
warning. When the speed is below the specified limit in
1-86 Trip Speed Low [RPM]
(except when starting or
stopping), the adjustable frequency drive will trip.
Warnings and Alarms
VLT
®
Refrigeration Drive Instruction Manual
8-10
MG16J122 - VLT
®
is a registered Danfoss trademark
8