10.3 Fuse Tables
10.3.1 Protection
Branch Circuit Protection
In order to protect the installation against electrical and
fire hazard, all branch circuits in an installation, switch
gear, machines, etc., must be short-circuited and
overcurrent protected according to national/international
regulations.
Short-circuit Protection
The adjustable frequency drive must be protected against
short-circuit to avoid electrical or fire hazard. Danfoss
recommends using the fuses mentioned below to protect
service personnel and equipment in case of an internal
failure in the adjustable frequency drive. The adjustable
frequency drive provides full short-circuit protection in
case of a short-circuit on the motor output.
Overcurrent Protection:
Provide overload protection to avoid fire hazard due to
overheating of the cables in the installation. The adjustable
frequency drive is equipped with internal overcurrent
protection that can be used for upstream overload
protection (UL applications excluded). See
4-18 Current
Limit
. Moreover, fuses or circuit breakers can be used to
provide the overcurrent protection in the installation.
Overcurrent protection must always be carried out
according to national regulations.
10.3.2 Fuse Selection
Danfoss recommends using the following fuses which will
ensure compliance with EN50178. In case of malfunction,
not following the recommendation may result in
unnecessary damage to the adjustable frequency drive.
The fuses below are suitable for use on a circuit capable of
delivering 100,000 Arms (symmetrical).
N110-N315
380–480 V
type aR
N75K–N400
525–690 V
type aR
Table 10.5
Power
Size
Fuse options
Bussman
PN
Littelfuse PN Littelfuse
PN
Bussmann
PN
Siba PN
Ferraz-Shawmut
PN
Ferraz-Shawmut PN
(Europe)
Ferraz-Shawmut PN
(North America)
N110
170M2619 LA50QS300-4 L50S-300
FWH-300A 20 610
31.315
A50QS300-4
6,9URD31D08A0315
A070URD31KI0315
N132
170M2620 LA50QS350-4 L50S-350
FWH-350A 20 610
31.350
A50QS350-4
6,9URD31D08A0350
A070URD31KI0350
N160
170M2621 LA50QS400-4 L50S-400
FWH-400A 20 610
31.400
A50QS400-4
6,9URD31D08A0400
A070URD31KI0400
N200
170M4015 LA50QS500-4 L50S-500
FWH-500A 20 610
31.550
A50QS500-4
6,9URD31D08A0550
A070URD31KI0550
N250
170M4016 LA50QS600-4 L50S-600
FWH-600A 20 610
31.630
A50QS600-4
6,9URD31D08A0630
A070URD31KI0630
N315
170M4017 LA50QS800-4 L50S-800
FWH-800A 20 610
31.800
A50QS800-4
6,9URD32D08A0800
A070URD31KI0800
Table 10.6 Fuse Options for 380–480 V Adjustable Frequency Drives
Specifications
VLT
®
Refrigeration Drive Instruction Manual