7.3 Wiring for External Alarm Reset
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB928.11
Function
Setting
Parameter 5-11 T
erminal 19
Digital Input
[1] Reset
* = Default value
Notes/comments:
Table 7.8 External Alarm Reset
7.4 Wiring for a Motor Thermistor
WARNING
THERMISTOR INSULATION
Risk of personal injury or equipment damage.
•
To meet PELV insulation requirements, use only
thermistors with reinforced or double
insulation.
Parameters
130BB686.12
VLT
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
A53
U - I
D IN
37
Function
Setting
Parameter 1-90
Motor Thermal
Protection
[2] Thermistor
trip
Parameter 1-93
Thermistor
Resource
[1] Analog
input 53
* = Default value
Notes/comments:
If only a warning is desired, set
parameter 1-90 Motor Thermal
Protection
to
[1] Thermistor
warning
.
Table 7.9 Motor Thermistor
Wiring Configuration Exampl...
VLT® Refrigeration Drive FC 103
60
Danfoss A/S © 04/2018 All rights reserved.
MG16P222