4.3.2 Status Word According to DSP 402
Profile
Output freq.
STW
Bit
no.:
Follower-master
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BA273.11
Illustration 4.4 Status Word
Bit
Bit value = 0
Bit value = 1
00
Not ready to switch
ON
Ready to switch ON
01
Switched OFF
Switched ON
02
Operation disabled
Operation enabled
03
No malfunction
Malfunction
04
Voltage disabled
Voltage enabled
05
Quick stop
Run
06
Switch on disable
Switch on enable
07
No warning
Warning
08
Reserved
09
Remote disabled
Remote enabled
10
Setpoint not reached
Setpoint reached
11
Speed limit not
active
Speed limit active
12
Reserved
13
Reserved
14
Not running
Running
15
Reserved
Table 4.7 Status Bits
Explanation of the status bits
Bit 00, Not ready to switch on/ready to switch on:
Bit 00 = 0 state less than Ready to switch on.
Bit 00 = 1 state at least = Ready to Switch on.
Bit 01, Switch off/switch on:
Bit 00 = 0 state less than switched on.
Bit 00 = 1 state at least = switched on.
Bit 02, Operation disable/operation enable:
Bit 00 = 0 state less than operation enable.
Bit 00 = 1 state at least = operation enable.
Bit 03, No fault/trip:
Bit 03 = 0 means that the frequency converter is not in a
fault condition.
Bit 03 = 1 means that the frequency converter has tripped
and needs a reset signal to run.
Bit 04, Voltage disable/voltage enable:
Bit 04 = 0 means that control word bit 01 = 1.
Bit 04 = 1 means that control word bit 01 = 0.
Bit 05, Quick stop/run:
Bit 05 = 0 means that control word bit 02 = 1.
Bit 05 = 1 means that control word bit 02 = 0.
Bit 06, Start enable/start disable:
Bit 06 = 0 state is not switch on disable.
Bit 06 = 1 state is switch on enable.
Bit 07, No warning/warning:
Bit 07 = 0 means that there is no warning. situation.
Bit 07 = 1 means that a warning has occurred.
Bit 08
Danfoss reserved.
Bit 09, Remote disable/remote enable:
Bit 09 = 0 means that the frequency converter has been
stopped with the [stop] key on the LCP, or that [Local] has
been selected in
parameter 3-13 Reference Site
.
Bit 09 = 1 means that it is possible to control the
frequency converter via the serial port.
Bit 10, Setpoint not reached/setpoint reached:
Bit 10 = 0 means that the actual motor speed is different
from the speed reference set. This can be the case while
the speed is ramped up/down during start/stop.
Bit 10 = 1 means that the present motor speed equals the
speed reference set.
Bit 11, Speed limit not active/speed limit active:
Bit 11 = 0 means that the output frequency is out of the
range set in
parameter 4-11 Motor Speed Low Limit [RPM]
/
parameter 4-12 Motor Speed Low Limit [Hz]
or
parameter 4-13 Motor Speed High Limit [RPM]
/
parameter 4-14 Motor Speed High Limit [Hz]
.
Bit 11 = 1 means that the output frequency is within the
mentioned range.
Bit 12
DSP 402 reserved.
Bit 13
DSP 402 reserved.
Bit 14, Running/not running:
Bit 14 = 0 means that the motor is not running.
Bit 14 = 1 means that the frequency converter has a valid
start signal or that the output frequency is greater than 0
Hz.
Bit 15
Danfoss reserved.
Control
Programming Guide
MG92G102