4.1.1 PDO Configuration
Index
Name
Sub
index
Description
Value Sub index 2
Transmission type
1400h
1
st
receive PDO (PDO 1)
0
Number of entries.
⇒
1...240
SYNC
1401h
2
nd
receive PDO (PDO 2)
1
COB ID.
⇒
1...240
SYNC
1402h
3
rd
receive PDO (PDO 3)
2
Transmission type.
⇒
254...255
COS
1403h
4
th
receive PDO (PDO 4)
⇒
254...255
COS
1600h
1
st
receive PDO mapping
(PDO 1)
COB-ID 201h–27Fh
0
Number of entries.
1
1
st
mapped object (60400010h control word, fixed) (
parameter 10-50 Process Data Config
Write.
[0])
1601h
2
nd
receive PDO mapping
(PDO 2)
COB-ID 301h–37Fh
0
Number of entries
1
1
st
mapped object (60400010h control word, fixed) (
parameter 10-50 Process Data Config
Write.
[0])
2
2
nd
mapped object (60420010h target velocity, fixed) (
parameter 10-50 Process Data Config
Write.
[1])
1602h
3
rd
receive PDO mapping
(PDO 3)
COB-ID 401h–47Fh
0
Number of entries.
1
1
st
mapped object (60400010h control word, fixed) (
parameter 10-50 Process Data Config
Write.
[0])
2
2
nd
mapped object (60420010h target velocity, fixed) (
parameter 10-50 Process Data Config
Write.
[1])
3
3
rd
mapped object (2000h + parameter number) (
parameter 10-50 Process Data Config
Write.
[2])
4
4
th
mapped object (2000h + parameter number) (
parameter 10-50 Process Data Config
Write.
[3])
1603h
4
th
receive PDO mapping
(PDO 4)
COB-ID 501h–57Fh
0
Number of entries.
1
5
th
mapped object (2000h + parameter number) (
parameter 10-50 Process Data Config
Write.
[4])
2
6
th
mapped object (2000h + parameter number) (
parameter 10-50 Process Data Config
Write.
[5])
3
7
th
mapped object (2000h + parameter number) (
parameter 10-50 Process Data Config
Write.
[6])
4
8
th
mapped object (2000h + parameter number) (
parameter 10-50 Process Data Config
Write.
[7])
Table 4.1 Receive PDO Configuration
Control
Programming Guide
MG92G102
Danfoss A/S © 06/2015 All rights reserved.
15