5.4 Local Control Panel (LCP) Operations
VLT
®
AutomationDrive FC 360 supports numerical local
control panel (NLCP) LCP 21, graphic local control panel
(GLCP) LCP 102, and blind cover. This chapter describes the
operations with LCP 21 and LCP 102.
NOTICE
The frequency converter can also be programmed from
the MCT-10 Set-up Software on PC via RS485 com-port.
This software can be ordered using code number
130B1000 or downloaded from the Danfoss website:
www.danfoss.com/BusinessAreas/DrivesSolutions/software-
download
.
5.4.1 Numerical Local Control Panel
The numerical local control panel LCP 21 is divided into 4
functional sections.
A. Numeric display.
B. Menu key.
C. Navigation keys and indicator lights (LEDs).
D. Operation keys and indicator lights (LEDs).
130BC506.10
Setup 1
A
B
C
D
5
12
13
14
15
10
11
10
9
6
7
8
4
1
2
3
Menu
Status
Quick
Menu
Main
Menu
Hand
On
Off
Reset
Auto
On
Back
OK
On
Warn
Alarm
Illustration 5.2 View of the LCP 21
A. Numeric display
The LCD display is backlit with 1 numeric line. All data is
shown in the LCP.
1
The set-up number shows the active set-up and the edit
set-up. If the same set-up acts as both active and edit set-
up, only that set-up number is shown (factory setting).
When active and edit set-ups differ, both numbers are
shown in the display (set-up 12). The number flashing
indicates the edit set-up.
2
Parameter number.
3
Parameter value.
4
Motor direction is shown at the bottom left of the display.
A small arrow indicates the direction.
5
The triangle indicates whether the LCP is in Status, Quick
Menu, or Main Menu.
Table 5.1 Legend to
, Section A
130BD135.10
Setup 1234
INDEX
AHP
VkW
srpm
Hz%
n2
n1
n3
p5
p4
p3
p2
p1
Illustration 5.3 Display Information
B. Menu key
To select between Status, Quick Menu, or Main Menu,
press [Menu].
C. Indicator lights (LEDs) and navigation keys
Indicator Light
Function
6
On
Green
ON turns on when the frequency
converter receives power from the
mains voltage, a DC bus terminal, or a
24 V external supply.
7
Warn
Yellow
When warning conditions are met, the
yellow WARN LED turns on, and text
appears in the display area identifying
the problem.
8
Alarm
Red
A fault condition causes the red alarm
LED to flash and an alarm text is
shown.
Table 5.2 Legend to
, Indicator Lights (LEDs)
Commissioning
VLT
®
AutomationDrive FC 360
22