Bit
Hex
Dec
Alarm word
(
parameter 1
6-90 Alarm
Word
)
Alarm word
2
(
parameter
16-91 Alarm
Word 2
)
Alarm word
3
(
parameter 1
6-97 Alarm
Word 3
)
Warning word
(
parameter 16-
92 Warning
Word
)
Warning word
2
(
parameter 16
-93 Warning
Word 2
)
Extended
status word
(
parameter 16-
94 Ext. Status
Word
)
Extended
status word 2
(
parameter 16-95 Ext
. Status Word 2
)
29
200000
00
53687091
2
Frequency
converter
initialized
Encoder loss
Reserved
Reserved
Back EMF too
high
Reserved
Heat sink clean
warning
30
400000
00
10737418
24
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
31
800000
00
21474836
48
Mech. brake
low
Reserved
Reserved
Reserved
Reserved
Database busy
Reserved
Table 8.19 Description of Alarm Word, Warning Word, and Extended Status Word
The alarm words, warning words, and extended status words can be read out via serial bus or optional fieldbus for
diagnosis.
Troubleshooting
PROFINET
56
Danfoss A/S © 04/2017 All rights reserved.
MG06G102
8
8